2017-09-06 12:17:222ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 2ND
 REQUEST
  
 1. WHAT IS WORKFORCE HOUSING IS THIS PROJECT FEDERALLY
 FUNDED. PER WPB AMEND TO FBC 107.2.1
  
 17. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB WATER
 METER. PER WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. SHT. A-6.5.1 THROUGH A-6.5.4 DETAIL 1 + 3 THE END OF
 THE GRAB BAR BACKING SHALL LINE UP WITH THE FRONT OF
 THE TUB. PER FHA DESIGN MANUAL PG 6.8-6.9 AS SHOWN ON
 DIAGRAM
  
 2. SHT. A-6.5.1 THROUGH A-6.5.4 DETAIL 2 THE TOP OF
 GRAB BAR BACKING SHALL MEASURE 38" OF FINISHED FLOOR.
 PER FHA DESIGN MANUAL PG 6.8-6.9 AS SHOWN ON DIAGRAM
  
 3. SHT. A-6.5.1 THROUGH A-6.5.4 THE CENTER LINE OF THE
 TOILET SHALL BE 18" OFF THE TUB OR WALL. FHA DESIGN
 MANUAL PG 6.7 - 7.43
  
 4. PLEASE PROVIDE PLUMBING FIXTURE SCHEDULE. PER WPB
 AMEND TO FBC 107.2.1
  
 5. ALL FLOOR DRAINS SHALL HAVE A TRAP PRIMER VALVE THE
 TRAP GUARD IS NOT APPROVED. PER FBC PL 1002.4 WHERE A
 TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP
 SEAL PRIMER VALVE SHALL BE INSTALLED. TRAP SEAL PRIMER
 VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE
 LEVEL OF THE TRAP SEAL. A TRAP SEAL PRIMER VALVE SHALL
 CONFORM TO ASSE 1018 OR ASSE 1044.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  