| 2017-09-06 12:17:22 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 2ND |
| | REQUEST |
| | |
| | 1. WHAT IS WORKFORCE HOUSING IS THIS PROJECT FEDERALLY |
| | FUNDED. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB WATER |
| | METER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. A-6.5.1 THROUGH A-6.5.4 DETAIL 1 + 3 THE END OF |
| | THE GRAB BAR BACKING SHALL LINE UP WITH THE FRONT OF |
| | THE TUB. PER FHA DESIGN MANUAL PG 6.8-6.9 AS SHOWN ON |
| | DIAGRAM |
| | |
| | 2. SHT. A-6.5.1 THROUGH A-6.5.4 DETAIL 2 THE TOP OF |
| | GRAB BAR BACKING SHALL MEASURE 38" OF FINISHED FLOOR. |
| | PER FHA DESIGN MANUAL PG 6.8-6.9 AS SHOWN ON DIAGRAM |
| | |
| | 3. SHT. A-6.5.1 THROUGH A-6.5.4 THE CENTER LINE OF THE |
| | TOILET SHALL BE 18" OFF THE TUB OR WALL. FHA DESIGN |
| | MANUAL PG 6.7 - 7.43 |
| | |
| | 4. PLEASE PROVIDE PLUMBING FIXTURE SCHEDULE. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. ALL FLOOR DRAINS SHALL HAVE A TRAP PRIMER VALVE THE |
| | TRAP GUARD IS NOT APPROVED. PER FBC PL 1002.4 WHERE A |
| | TRAP SEAL IS SUBJECT TO LOSS BY EVAPORATION, A TRAP |
| | SEAL PRIMER VALVE SHALL BE INSTALLED. TRAP SEAL PRIMER |
| | VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE |
| | LEVEL OF THE TRAP SEAL. A TRAP SEAL PRIMER VALVE SHALL |
| | CONFORM TO ASSE 1018 OR ASSE 1044. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |