2017-09-06 10:13:282ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060189
 9/6/17
  
 1) THE ENERGYGAUGE SUMMIT IECC COMPLIANCE FORM DOES NOT
 INCLUDE DATA FOR THE ACCU- AHU #1, 2, & 3 SYSTEM.
  
 2) PLEASE SEE COMMENT #3 FROM THE 1ST REVIEW AND
 SECTION C407.5.2.3 FBC-14 ENERGY CONSERVATION- PROVIDE
 AC CALCULATIONS USING ONE THERMAL BLOCK PER SPACE, OR
 ONE THERMAL BLOCK FOR MULTIPLE SPACES THAT ARE FACING
 THE SAME ORIENTATIONS. PLEASE NOTE THAT CORNER UNITS
 AND UNITS WITH ROOFS OR FLOOR LOADS SHALL ONLY BE
 COMBINED WITH UNITS SHARING THE SAME FEATURES. IN
 ADDITION
  
 PLEASE REFER TO SECTION C403.2.1: DESIGN LOADS SHALL BE
 DETERMINED IN ACCORDANCE WITH THE PROCEDURES DESCRIBED
 IN THE ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N AND
 SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED
 TO THE BUILDING DEPARTMENT.
  
 3) M-4: PLEASE ENLARGE THE AC EQUIPMENT SCHEDULE FOR
 THE APARTMENT UNITS AND NUMBER THEM AS EITHER AC-1 OR 2
 AS THEY ARE SHOWN ON THE DRAWINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  