2017-09-05 12:29:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ADDRESS NUMBER ON PERMIT APPLICATION IS 2191, ON
 COVER SHEET IS 2181, AND ON ELECTRICAL SHEETS IS 2180.
 PROVIDE CORRECT ADDRESS ON PLANS. FBC 107.2.1
 2. SHEET E-8 SHOWS 6 SETS OF 750 KCMIL CU FOR SERVICE
 FEEDERS, WHILE SHEET E-6 SHOWS 7 SETS OF 600 KCMIL CU.
 CORRECT DISCREPANCY. FBC 107.2.1
 3. LOAD CALCULATION FOR MDP SHOWS SEVERAL DIFFERENT
 CALCULATIONS (ONE STORY, TWO STORY, ETC.). PROVIDE LOAD
 CALCULATION RELATED TO THIS PERMIT ONLY FOR THE SIX
 STORY BUILDING. REMOVE ALL OTHER UNRELATED INFORMATION.
 ADDITIONALLY, THE LOAD VA SHOWN FOR THE 1 BEDROOM UNIT
 IS THE SAME AS FOR THE 2 BEDROOM UNIT. LOAD CALCULATION
 FOR PANEL H IS DIFFERENT THAN LISTED IN PANEL SCHEDULE.
 PROVIDE CORRECTIONS. NEC 220; FBC 107.2.1
 4. PANEL H SHOWS A JOCKEY PUMP ON CIRCUIT 19, 21, 23.
 IS THIS THE JOCKEY PUMP FOR THE FIRE PUMP SYSTEM? IF
 SO, THIS CANNOT BE FEED FROM PANEL H. THE JOCKEY PUMP
 SPECIFIED ON SHEET FP 2.0 IS NOT SHOWN ON RISER DIAGRAM
 WITH FIRE PUMP. PROVIDE CORRECTION. NEC 215.5,
 695.4(B)(3); FBC 107.2.1
 5. FIRE PUMP SERVICE IS NOT LABELED AS ONE OF THE MAINS
 FOR THE BUILDING. PROVIDE CORRECTION. NEC 230.2(E)
 6. PANEL H LOAD CALCULATION STATES THAT THE FIRST 10K
 VA ARE AT 100%. HOWEVER, THE LOAD SHOWN IS 4320 VA, NOT
 10,000. PANEL H1 LOAD CALCULATION IS SIMILARLY WRONG.
 PROVIDE CORRECTION. NEC 220.44
 7. PROVIDE DETAILS OF SECOND POWER SOURCE REQUIRED FOR
 FIRE PUMP. NEC 695.3(B)
 8. PROVIDE LOAD CALCULATION FOR FIRE PUMP CONTROLLER
 AND ASSOCIATED EQUIPMENT TO VERIFY FEEDER, GROUNDING,
 AND OVERCURRENT PROTECTION REQUIREMENTS. NEC 695.6
 9. PLAN STATES THAT THE LOCKED ROTOR CURRENT FOR THE
 FIRE PUMP MOTOR IS 32.2 AMPS. ACCORDING TO TABLE
 430.251(B), THE LOCKED ROTOR CURRENT FOR A MOTOR THIS
 SIZE SHOULD BE 179 AMPS. PROVIDE CORRECTION. NEC TABLE
 430.251(B); FBC 107.2.1
 10. PLAN INCLUDES ELECTRICAL PLAN FOR 1ST FLOOR, 4TH
 FLOOR, AND ROOF ONLY. PROVIDE FULL SET OF PLANS FOR
 REVIEW. FBC 107.2.1, 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER