| Plan Review Notes For Permit 17060189 |
| Permit Number |
17060189 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-09-13 16:05:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 17060191 APARTMENT BUILDING # | | | 17060189 APARTMENT BUILDING, 2191 N AUSTRALIAN AVE (SIX | | | STORY) | | | 17060192 CLUBHOUSE BUILDING | | | | | | COMMENTS FROM PREVIOUS REVIEW; UNABLE TO LOCATE A | | | RESPONSE LETTER; EMAILED APPLICANT. | | | | | | 1-2. OK | | | | | | 3. ADDRESS PLUMBING COMMENTS REGARDING FAIR HOUSING AS | | | THEY ARE APPLICABLE FOR BUILDING REVIEW. | | | | | | 4. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION | | | REPORT. 2ND REQUEST. | | | | | | 5-8. OK | | | | | | 9. FBC B 1207.2, 1207.3, REVISE COVER PAGE TO INCLUDE | | | FLOORING UNDERLAYMENT AS AN ITEM TO BE SUBMITTED AT A | | | LATER TIME. | | | | | | 12-13. OK | | | | | | 14. THIS PERMIT WILL BE ISSUED WITH PROVISOS: | | | | | | A. SEPARATE PERMITS REQUIRED FOR FENCING, SITE WALLS, | | | SIGNAGE, PARKING LOT/PAVING, DUMPSTER ENCLOSURE. | | | | | | B. FLOORING UNDERLAYMENT TEST REPORTS (STC, IIC, FLAME | | | SPREAD) REQUIRED TO BE SUBMITTED PRIOR TO INSTALLATION. | | | | | | C. SEPARATE ROOF PERMIT REQUIRED. NOA 15-1026.04 WAS | | | SUBMITTED; WHEN SUBMITTING ROOF PERMIT APPLICATION, | | | INDICATE ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF | | | REQUIRED. | | | |
|