Plan Review Notes
Plan Review Notes For Permit 17060189
Permit Number 17060189
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-30 11:35:361ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WHAT IS WORKFORCE HOUSING IS THIS PROJECT FEDERALLY
 FUNDED. PER WPB AMEND TO FBC 107.2.1
  
 2, SHT. A-1.4 LABEL ROOF AREAS ON THE PLAN THAT YOU
 REFERENCE IN YOU ROOF DRAIN CALCULATIONS. PER WPB AMEND
 TO FBC 107.2.1
  
 3. PLEASE CLARIFY ON THE PLAN WHICH DESIGN
 SPECIFICATION A OR B THAT YOU WILL BE USING ON EACH
 UNIT. PER FHA
  
 4. PLEASE INDICATE ON THE PLAN WHICH DOCUMENT THE FHA
 DESIGN MANUAL OR THE FHA GUIDELINES FOUND IN FBC ACC,
 YOU WILL BE USING TO DESIGN THE ELEMENTS TO COMPLY WITH
 THE FHA . PER WPB AMEND TO FBC 107.2.1
  
 5. SHOW THE CLEAR FLOOR SPACE FOR THE FIXTURES IN THE
 BATHROOM AND KITCHEN. PER FHA
  
 6. SHT. A-6.10 DETAIL 1.7 SHOWS A 20" X 4" SCUPPER
 SHTA-1.4 THE SCUPPER IS SHOWN AT 6" X 12' PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 7. TRAP PRIMERS REQUIRED ON ALL FLOOR DRAINS. PER FBC
 PL 1002.4
  
 8. PLEASE SHOW ON THE PLANS THE SQUARE FOOTAGE BEING
 DRAINED BY EACH ROOF DRAIN . PER WPB AMEND TO FBC
 107.2.1
  
 9. TERMINATION OF THE PAN DRAINS SHALL COMPLY WITH FBC
 PL 504.7.2 PAN DRAIN TERMINATION.
 THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER
 A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR
 DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE
 THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE.
  
 10. PLEASE SHOW DETAIL OF KITCHEN RISER THE WAY IT IS
 NOW I CAN NOT DETERMINE HOW YOU ARE DESIGNING IT. PER
 WPB AMEND TO FBC 107.2.1
  
 11. LABEL THE RISERS ON SHT P-8. PER WPB AMEND TO FBC
 107.2.1
  
 12. PROVIDE DETAIL FOR FLUSHING RING ON TRASH-SHOOT .
 PER WPB AMEND TO FBC 107.2.1
  
 13. SHOW FLUSHRING ON WATER RISER. PER WPB AMEND TO FBC
 107.2.1
  
 14. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUMP PIT
 PUMP AND BOOSTER PUMPS. PER WPB AMEND TO FBC 107.2.1
  
 15. SHT. A-6.5.4 AND A-6.5.3 DETAIL B(L) B(R) IF YOU
 ARE YOU ARE USING THE B SPECIFICATIONS FOR THESE UNITS
 IT SHALL HAVE A CLEAR FLOOR SPACE FOR A PARALLEL
 APPROACH TO THE TUB. PER FHA
  
 16. THE BACKING FOR THE GRAB BAR ON THE SIDE WALL OF
 THE TUB SHALL START 6" MAX FROM THE TOP OF THE TUB AND
 EXTEND UP TO A MIN OF 38" OFF THE FLOOR. PER FHA
  
 17. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB WATER
 METER. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  