| 2017-07-03 09:55:19 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | PERMIT #17060189 |
| | 7/3/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE LOUVERED AC CLOSETS DOORS SHALL BE |
| | NON-COMBUSTIBLE PER SECTION C403.2.7.2 FBC-14 ENERGY |
| | CONSERVATION. THE DOOR SCHEDULE ON SHEET A-8.1 |
| | INDICATES WOOD DOORS. |
| | |
| | 2) THE SUBMITTED ENERGYGAUGE FORM R405-2014 IS A |
| | RESDIENTIAL COMPLIANCE FORM, HOWEVER THE PROPOSED |
| | PROJECT IS A COMMERCIAL BUILDING- SEE SECTION C202 & |
| | R202 DEFINITIONS FBC-14 ENERGY CONSERVATION. PLEASE SEE |
| | SECTIONS C101.5 & C407.4.1 AND SUBMIT A COMMERCIAL |
| | COMPLIANCE FORM. |
| | |
| | 3) THE SUBMITTED ENERGYGAUGE FORM R405-2014 IS |
| | SPECIFYING A WORST CASE METHOD, HOWEVER THAT METHOD IS |
| | NOT APPLICABLE TO A COMMERCIAL BUILDING PROJECT. PLEASE |
| | SEE SECTIONS C407.4.2- C407.5.2.3 FOR THERMAL ZONING |
| | BLOCKS USING DEFINED HVAC ZONES ON THE PLANS, OR |
| | UNDEFINED ZONES. |
| | |
| | 4) SHEET M-3: CONTRARY TO THE NOTE ON THE ROOF PLAN |
| | THERE ARE NO STRUCTURAL DETAILS FOR MOUNTING THE AC |
| | STANDS AND CONDENSER TO THE ROOF STRUCTURE. PLEASE |
| | PROVIDE THE WIND LOAD DESIGN CRITERIA AND STRUCTURAL |
| | DETAILS PER SECTION 301.15 FBC-14 MECHANICAL. |
| | ADDITIONALLY, THE ENGINEER OF RECORD SHALL CIRCLE, |
| | HIGHLIGHT, OR OTHERWISE MARKUP THE AC STAND NOA TO SHOW |
| | THE APPLICABLE |
| | INSTALLATION DETAILS. PLEASE INDICATE THE STAND |
| | CONFIGURATION, STAND ANCHORING TO THE ROOF, AND |
| | CONDENSER ANCHORING TO THE STAND. |
| | |
| | 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | APARTMENTS IN COMPLIANCE WITH TABLE 403.3 OR TABLE 6-1 |
| | ASHRAE 62.1. INDICATE THE REQUIRED AND PROVIDE |
| | VENTILATION RATES. |
| | |
| | 6) PROVIDE MINIMUM VENTILATION CALCULATIONS AND |
| | VENTILATION PLANS FOR THETRASH COMPACTOR ROOM, THE |
| | ELECTRICAL ROOMS, AND THE PUMP ROOM- SEE TABLE 403.3. |
| | PLEASE NOTE THAT TABLE 6-4 ASHRAE 62.1 REQUIRES AN |
| | EXHAUST SYSTEM FOR THE TRASH COMPACTOR ROOM DESIGNED AT |
| | A RATE OF 1 .00 CFM PER SQ. FT. |
| | |
| | 7) INDICATE HOW THE ELEVATOR HOISTWAY WILL BE VENTED IN |
| | ACCORDANCE WITH SECTION 3004 FBC-14 BUILDING. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |