2017-07-03 09:55:191ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17060189
 7/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LOUVERED AC CLOSETS DOORS SHALL BE
 NON-COMBUSTIBLE PER SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION. THE DOOR SCHEDULE ON SHEET A-8.1
 INDICATES WOOD DOORS.
  
 2) THE SUBMITTED ENERGYGAUGE FORM R405-2014 IS A
 RESDIENTIAL COMPLIANCE FORM, HOWEVER THE PROPOSED
 PROJECT IS A COMMERCIAL BUILDING- SEE SECTION C202 &
 R202 DEFINITIONS FBC-14 ENERGY CONSERVATION. PLEASE SEE
 SECTIONS C101.5 & C407.4.1 AND SUBMIT A COMMERCIAL
 COMPLIANCE FORM.
  
 3) THE SUBMITTED ENERGYGAUGE FORM R405-2014 IS
 SPECIFYING A WORST CASE METHOD, HOWEVER THAT METHOD IS
 NOT APPLICABLE TO A COMMERCIAL BUILDING PROJECT. PLEASE
 SEE SECTIONS C407.4.2- C407.5.2.3 FOR THERMAL ZONING
 BLOCKS USING DEFINED HVAC ZONES ON THE PLANS, OR
 UNDEFINED ZONES.
  
 4) SHEET M-3: CONTRARY TO THE NOTE ON THE ROOF PLAN
 THERE ARE NO STRUCTURAL DETAILS FOR MOUNTING THE AC
 STANDS AND CONDENSER TO THE ROOF STRUCTURE. PLEASE
 PROVIDE THE WIND LOAD DESIGN CRITERIA AND STRUCTURAL
 DETAILS PER SECTION 301.15 FBC-14 MECHANICAL.
 ADDITIONALLY, THE ENGINEER OF RECORD SHALL CIRCLE,
 HIGHLIGHT, OR OTHERWISE MARKUP THE AC STAND NOA TO SHOW
 THE APPLICABLE
 INSTALLATION DETAILS. PLEASE INDICATE THE STAND
 CONFIGURATION, STAND ANCHORING TO THE ROOF, AND
 CONDENSER ANCHORING TO THE STAND.
  
 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 APARTMENTS IN COMPLIANCE WITH TABLE 403.3 OR TABLE 6-1
 ASHRAE 62.1. INDICATE THE REQUIRED AND PROVIDE
 VENTILATION RATES.
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS AND
 VENTILATION PLANS FOR THETRASH COMPACTOR ROOM, THE
 ELECTRICAL ROOMS, AND THE PUMP ROOM- SEE TABLE 403.3.
 PLEASE NOTE THAT TABLE 6-4 ASHRAE 62.1 REQUIRES AN
 EXHAUST SYSTEM FOR THE TRASH COMPACTOR ROOM DESIGNED AT
 A RATE OF 1 .00 CFM PER SQ. FT.
  
 7) INDICATE HOW THE ELEVATOR HOISTWAY WILL BE VENTED IN
 ACCORDANCE WITH SECTION 3004 FBC-14 BUILDING.
  