Plan Review Notes For Permit 17060189
Permit Number 17060189
Review Stop E
Sequence Number 1
Notes
Date Text
2017-07-03 15:29:16FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-6 NEED TO SIZE THE FIRE PUMP AND CONTROLER
  
 PAGE E-6 NEED TO SUPPLY AN INTYERSYSTEM BONDING STRIP
 AT EAC SERVICE LOCATION PER 250.94
  
 PAGE E-8 NO SITE LIGHT CIRCUITS SHOWN, ARE THERE ANY
 FIXTURES ON THE BUILDING?