| 2017-07-17 15:35:43 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 17060191 APARTMENT BUILDING # |
| | 17060189 APARTMENT BUILDING A (SIX STORY) |
| | 17060192 CLUBHOUSE BUILDING |
| | |
| | 1. ALL PAGES HAVE AN INCORRECT ADDRESS AND NOT ALL ARE |
| | CONSISTENT WITH EACH OTHER (DIFFERENT INCORRECT |
| | ADDRESSES). FBC 107, PLEASE CORRECT THE ADDRESS ON EACH |
| | PAGE. |
| | |
| | 2. FS471.0195, THE DBPR RECORD FOR THE FOLLOWING |
| | ENGINEER(S) DO NOT REFLECT THAT THE ADVANCED FLORIDA |
| | BUILDING CODE COURSE HAS BEEN COMPLETED. EMAIL THE |
| | CERTIFICATE TO FBPE AND REQUEST THAT THE DBPR RECORD BE |
| | UPDATED. NOTE THAT IT IS POSSIBLE THAT THE COURSE WAS |
| | COMPLETED AND THE WEBSITE IS NOT CURRENT. |
| | |
| | SANTIAGO ARANEGUI, PE |
| | JOE SPASOVSKI, PE |
| | |
| | PERMIT ISSUANCE WILL NOT BE DELAYED DUE TO THIS |
| | COMMENT. HOWEVER, FLORIDA STATUTE REQUIRES THAT: |
| | LOCAL JURISDICTIONS SHALL BE RESPONSIBLE FOR NOTIFYING |
| | THE BOARD WHEN DESIGN DOCUMENTS ARE SUBMITTED FOR |
| | BUILDING CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN |
| | COMPLIANCE WITH THIS SECTION. |
| | |
| | 3. ADDRESS OTHER TRADES' COMMENTS REGARDING FAIR |
| | HOUSING AS THEY ARE APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 4. FBC B 1803, PROVIDE THE GEOTECHNICAL INVESTIGATION |
| | REPORT. THIS IS AREA IS KNOWN TO HAVE THE POTENTIAL OF |
| | POOR SOILS. |
| | |
| | 5. SECTION 5-A6.6.2, REVISE PLAN TO SHOW FRT (LUMBER) |
| | OR REVISE PLAN TO INCLUDE APPLICABLE EXCEPTION, FBC B |
| | 602. REVISE OTHER LOCATIONS WHICH SHOW WOOD (SUCH AS |
| | MUTIPLE DETAILS, S3.5). |
| | |
| | 6. S1.0, ROOF LIVE LOAD IS 20PSF; FBC B TABLE 1607.1 |
| | REQUIRES 300 CONCENTRATED FOR "ALL ROOF SURFACES |
| | SUBJECT TO MAINTENANCE WORKERS". RTU EQUIPMENT SHOWN. |
| | EITHER REVISE DESIGN CRITERIA FOR THIS ROOF SECTION OR |
| | PROVIDE RATIONALE FOR 20PSF LIVE LOAD. |
| | |
| | 7. IT APPEARS THAT NOT ALL LAP SPLICES WERE SPECIFIED |
| | ON THE PLAN FOR THE FOUNDATION; REVISE PLAN OR ADVISE |
| | WHERE THIS CAN BE LOCATED, FBC 107, FBC B CHAPTER 19. |
| | |
| | 8. FBC B 420.3, PROVIDE A DETAIL SHOWING COMPLIANCE |
| | WITH THE 1 HOUR SEPARATION REQUIREMENT FOR THE |
| | FLOOR/CEILING ASSEMBLIES BETWEEN UNITS. REVISE THE PLAN |
| | TO SHOW THE 1 HOUR (MINIMUM) FLOOR/CEILING ASSEMBLY. |
| | |
| | 9. FBC B 1207.2, 1207.3, PROVIDE TEST REPORTS FOR THE |
| | FLOORING UNDERLAYMENT (STC/IIC). REVISE PLAN TO INCLUDE |
| | REQUIREMENT FOR ACOUSTIC INSULATION. NOTE THAT SPEC |
| | SHEETS ARE NOT ACCEPTABLE; ACTUAL TEST REPORTS ARE |
| | REVIEWED. IT IS LIKELY THAT THE MANUFACTURER WILL BE |
| | REQUIRED TO DO A COMPARATIVE ANALYSIS AS IT IS UNLIKELY |
| | THAT THE UNDERLAYMENT WAS TESTED WITH HOLLOW CORE (MOST |
| | TESTS ARE DONE WITH A CONCRETE SLAB). |
| | |
| | CSM CRACK SUPPRESSION & SOUND CONTROL SPEC SHEET WAS |
| | PROVIDED. PLEASE SEND TEST REPORTS VIA EMAIL FOR |
| | PRELIMINARY REVIEW. WHEN REVISING PLAN TO INCLUDE |
| | UNDERLAYMENT REQUIREMENT, IT IS ADVISED THAT YOU DO NOT |
| | SPEC A PRODUCT. |
| | |
| | 10. FBC 720.2, PROVIDE A COPY OF THE FLAME SPREAD TEST |
| | FOR THE PROPOSED FLOORING UNDERLAYMENT. |
| | |
| | 11. AS THIS IS NEW CONSTRUCTION, APPLY FOR AN |
| | ENGINEERING PERMIT; 561-494-1040. ENGINEERING |
| | DEPARTMENT APPROVAL IS REQUIRED PRIOR TO PERMIT |
| | ISSUANCE. CONTACT THEM DIRECTLY REGARDING REQUIREMENTS. |
| | IF YOU HAVE ALREADY APPLIED, PROVIDE THE APPLICATION |
| | NUMBER. I WAS UNABLE TO LOCATE AN ENGINEERING |
| | APPLICATION FOR THIS PARCEL ID. |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 12. A SEPARATE ROOF PERMIT IS REQUIRED. A ROOF PRODUCT |
| | APPROVAL WAS SUBMITTED, FIBERTITE SINGLE PLY ROOF |
| | SYSTEMS OVER LIGHTWEIGHT CONCRETE DECKS (NOA |
| | 15-1026.04). |
| | |
| | FBC 1609, AT THIS TIME, APPLICANT MAY INDICATE WHICH |
| | APPROVED ASSEMBLY IS PROPOSED. IF THIS IS DONE NOW, THE |
| | ROOF SUB PERMIT WILL BE ISSUED WITHOUT ANY OTHER |
| | INFORMATION REQUIRED. |
| | |
| | IF APPLICANT DOES NOT PROVIDE THIS INFORMATION AT THIS |
| | TIME, THIS PERMIT WILL BE ISSUED WITH PROVISO THAT, AT |
| | TIME OF ROOF SUB PERMIT APPLICATION, THE APPROVED |
| | ASSEMBLY IS TO BE SELECTED. A PLAN REVIEW WILL BE |
| | REQUIRED AT THAT TIME. |
| | |
| | 13. WHEN AVAILABLE, PROVIDE A COPY OF THE CONTRACT FOR |
| | THE THREE PROPOSED BUILDINGS, FBC 109. |
| | |
| | 14. THIS PERMIT WILL BE ISSUED WITH PROVISOS: |
| | |
| | A. SEPARATE PERMITS REQUIRED FOR FENCING, SITE WALLS, |
| | SIGNAGE, PARKING LOT/PAVING, DUMPSTER ENCLOSURE, |
| | |
| | |
| | |