2017-06-14 16:11:341ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DIMENSION TO SHOW COMPLIANCE OF FIXTURE
 CLEARANCE. PER FBC PL P2705.1 GENERAL.
 THE INSTALLATION OF FIXTURES SHALL CONFORM TO THE
 FOLLOWING: 5. WATER CLOSETS, LAVATORIES AND BIDETS. A
 WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE SET CLOSER
 THAN 15 INCHES (381 MM) FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION OR VANITY OR CLOSER THAN 30 INCHES (762
 MM) CENTER-TO-CENTER BETWEEN ADJACENT FIXTURES. THERE
 SHALL BE A CLEARANCE OF NOT LESS THAN 21 INCHES (533
 MM) IN FRONT OF A WATER CLOSET, LAVATORY OR BIDET TO
 ANY WALL, FIXTURE OR DOOR.
  
 2. PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND TO FBC
 107.3.5.3(11)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  