| Plan Review Notes For Permit 17060186 |
| Permit Number |
17060186 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-16 14:41:21 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17060186 | | | 6/16/17 | | | | | | 1) SHOW THE NEW BATH EXHAUST DUCT RUN AND TERMINATION | | | LOCATION. | | | | | | 2) IDENTIFY AND LABEL THE NEW ROOM OR SPACE TO THE WEST | | | OF THE NEW BATHROOM. CLARIFY IF THIS TO REMAIN AN | | | ENCLOSED PORCH OR A NEW ROOM. CLARIFY IF THE NEW ROOMS | | | WILL BE AIR CONDITIONED. | | | | | | 3) THE NEW BATHROOM, AND ADJOINING ROOM ARE CLASSIFIED | | | AS AN ADDITION PER SECTION 202 FBC-14 RESIDENTIAL. | | | PLEASE REFER TO SECTION R101.4.3 FBC-14 ENERGY | | | CONSERVATION AND SUBMIT ENERGY CALCULATIONS- SEE | | | SECTION R101.5.1 FOR COMPLIANCE MATERIALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|