| Plan Review Notes For Permit 17060176 |
| Permit Number |
17060176 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-20 16:42:49 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17060176 | | | 6/20/17 | | | | | | PLAN REVIEW RESULT: DENIED. | | | | | | 1) M-201: SHOW THE LOCATION(S) OF REQUIRED SMOKE | | | DETECTORS IN THE RETURN AIR SYSTEM(S)- SEE SECTIONS | | | 606.2.1 & 606.2.2. | | | | | | 2) M-201: SHOW THE LOCATIONS OF THE REQUIRED OUTSIDE | | | AIR DAMPERS FOR THE SYSTEMS- SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|