Plan Review Notes
Plan Review Notes For Permit 17060176
Permit Number 17060176
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-20 16:42:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060176
 6/20/17
  
 PLAN REVIEW RESULT: DENIED.
  
 1) M-201: SHOW THE LOCATION(S) OF REQUIRED SMOKE
 DETECTORS IN THE RETURN AIR SYSTEM(S)- SEE SECTIONS
 606.2.1 & 606.2.2.
  
 2) M-201: SHOW THE LOCATIONS OF THE REQUIRED OUTSIDE
 AIR DAMPERS FOR THE SYSTEMS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  