| 2017-06-29 18:21:10 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PAGE E-1 |
| | |
| | FOR ALL MODULAR FURNITURE |
| | |
| | ASHREA 90.1 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT |
| | LEAST 50% OF ALL 125 VOLT 15- AND 20-AMPERE |
| | RECEPTACLES, INCLUDING THOSE |
| | INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE |
| | FOLLOWING SPACE TYPES: A. PRIVATE OFFICES B. OPEN |
| | OFFICES C. COMPUTER CLASSROOMS |
| | SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT |
| | SHALL FUNCTION ON: A. A SCHEDULED BASIS USING A |
| | TIME-OF-DAY OPERATED CONTROL |
| | DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC |
| | PROGRAMMED TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL |
| | BE PROVIDED FOR AREAS OF NO |
| | MORE THAN 25,000 FT2 BUT NOT MORE THAN ONE FLOOR, OR B. |
| | AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF |
| | WITHIN 30 MINUTES OF ALL |
| | OCCUPANTS LEAVING A SPACE, OR C. A SIGNAL FROM ANOTHER |
| | CONTROL OR ALARM SYSTEM THAT INDICATES THE AREA IS |
| | UNOCCUPIED. EXCEPTIONS: |
| | RECEPTACLES FOR THE FOLLOWING SHALL NOT REQUIRE AN |
| | AUTOMATIC CONTROL DEVICE: A. RECEPTACLES SPECIFICALLY |
| | DESIGNATED FOR EQUIPMENT |
| | REQUIRING 24 HOUR OPERATION. B. SPACES WHERE AN |
| | AUTOMATIC SHUTOFF WOULD ENDANGER THE SAFETY OR SECURITY |
| | OF THE ROOM OR BUILDING |
| | OCCUPANT(S) |
| | |
| | LOUNGE ROOM |
| | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL |
| | ALL OUTLETS INSTALLED WITHIN 6' OF THE SINK. |
| | (B) OTHER THAN DWELLING UNITS (5) SINKS WHERE |
| | RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) |
| | |
| | |
| | |