Plan Review Notes
Plan Review Notes For Permit 17060150
Permit Number 17060150
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-07-12 11:53:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN DOES NOT SHOW DETAIL OF THE CHAIR IN THE
 RESTING POSITION AT THE BOTTOM OF THE STAIRS. WHAT ARE
 THE DIMENSION OF THE LANDING, WHERE IS THE CHAIR IN
 RELATION TO THE LANDING AND EXIT DOOR AND WHAT IS THE
 DOOR SWING LOCATION?
  
 PLEASE PROVIDE.
  
  
 2) THE PLAN DOES NOT INDICATE THE REQUIRED MINIMUM
 EGRESS DIMENSION OF THE EXIT STAIR; 36" ? DOES THIS
 INSTALLTION IMPACT THE REQUIRED MINIMUM EGRESS WIDTH:
 36"?
  
 PLEASE JUSTIFY AND PROVIDE DETAILS.
  
  
 3) DOES THIS INSTALLTION IMPACT THE HANDRAIL ON THE
 SIDE IT IS INSTALLED?
  
 PLEASE PROVIDE DETAILS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  