Plan Review Notes
Plan Review Notes For Permit 17060134
Permit Number 17060134
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-13 07:40:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060134
 6/13/17
  
 1) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE
 OUTDOOR AIR INTAKE OPENINGS TO PROPERTY LINES,
 BUILDINGS ON THE SAME LOT, STREETS, ALLEYS, PARKING
 LOTS, AND EXHAUST OUTLETS- SEE SECTION 401.4 AND
 501.3.1.
  
 2) THE SUBMITTED AC CALCULATIONS INDICATE THE 10KW HEAT
 STRIPS ARE OVERSIZED FOR THE CALCULATED LOADS OF
 APPROXIMATELY 7.0KW- SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION.
  
 3) SHEET M1: PROVIDE DUCT SMOKE DETECTORS IN THE RETURN
 AIR SYSTEMS OF AC SYSTEMS 1 & 2. THIS REQUIREMENT IS
 BASED ON THE FACT THAT A TYPICAL 5-TON SYSTEM CAN
 PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION 606.2.1.
  
 4) M1: THE 24X24" RETURN AIR GRILL FOR AC #2 IS
 UNDERSIZED FOR 2000 CFMS OF AIR: 50 SQ. INCHES PER 100
 CFMS, OR 200 SQ. INCHES PER TON ARE BASIC SIZING RULES
 OF THUMB- SEE SECTION 601.5.
  
 5) M1: THE 70 CFM AC DROP IN THE INTERIOR EXIT STAIRWAY
 IS PROHIBITED PER SECTION 601.3.
  
 6) M1: THE 4" DUCT SUPPLYING JARRET'S BATHROOM IS
 PROHIBITED FROM PASSING THROUGH THE INTERIOR STAIRWAY
 ENCLOSURE- SECTION 601.3.
  
 7) M1: PENDING REVIEW AND REVISED PLANS PER BUILDING
 AND FIRE COMMENTS, THE DUCT DROPS FROM AC #1 FROM THE
 2ND FLOOR TO THE 1ST FLOOR MAY BE REQUIRED TO BE IN A
 SHAFT ENCLOSURE, OR BE PROVIDED WITH FIRE DAMPOERS
 WHERE THEY PENETRATE THE FLOOR/CEILING ASSEMBLY- SEE
 SECTIONS 607.6- 607.7.
  
 8) PLEASE NOTE THAT ADDITIONAL REVIEW COMMENTS MAY
 OCCUR WHEN CORRECTED PLANS ARE SUBMITTED. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  