| 2017-06-12 14:05:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 1 - THE OCCUPANCY CLASSIFICATION IS |
| | INDICATED AS BUSINESS; HOWEVER, THERE APPEARS TO BE |
| | SEVERAL ASSEMBLY SPACES THAT APPEAR TO ME MORE THAN |
| | INCIDENTAL. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPANCIES |
| | |
| | 38.1.7 OCCUPANT LOAD. THE OCCUPANT LOAD, IN NUMBER OF |
| | PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS |
| | ARE REQUIRED, SHALL BE DETERMINED ON THE BASIS OF THE |
| | OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE |
| | CHARACTERISTIC OF THE USE OF THE SPACE, OR SHALL BE |
| | DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF THE |
| | SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER. |
| | |
| | PER NFPA 101, CHAPTER 6, OCCUPANCY CALSSIFICATION. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY |
| | TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY |
| | SHALL BE TREATED AS A MIXED OCCUPANCY. |
| | |
| | 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS |
| | REQUIRED BY TABLE 508.2.5 OF THE FLORIDA BUILDING CODE |
| | WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| | INCIDENTAL USE AREA SHALL BE SEPARATED BY CONSTRUCTION |
| | CAPABLE OF RESISTING THE PASSAGE OF SMOKE. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| | RESISTANCE?RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | |
| | |
| | PLEASE REVIEW AND CLARIFY THE OCCUPNACY CLASSIFICATION |
| | AND ENSURE THE CONSTRUCTION FEATURES MEET THOSE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 1 - A LULU ELEVATOR IS NOTED. |
| | |
| | PER NFPA 101, CHAPTER 38 |
| | |
| | 38.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. ELEVATORS, |
| | ESCALATORS, AND CONVEYORS SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTION 9.4. |
| | |
| | 9.4.2 CODE COMPLIANCE. |
| | 9.4.2.1 EXCEPT AS MODIFIED HEREIN, NEW ELEVATORS, |
| | ESCALATORS, DUMBWAITERS, AND MOVING WALKS SHALL BE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF ASME A17.1/CSA B44, |
| | SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. |
| | |
| | THERE DOES NOT APPEAR TO BE ANY SPEC SHEETS FOR THE |
| | PROPOSED ELEVATOR AND ONE ANY INFORMATION THAT IT |
| | COMPLIES WITH THE REQUIREMENTS. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE IS AN AREA OF REFUGE INDICATED AT |
| | THE TOP OF THE STAIRWAY. |
| | |
| | PER NFPA 101, CHAPTER 3, DEFINITIONS |
| | |
| | 3.3.22* AREA OF REFUGE. AN AREA THAT IS EITHER (1) A |
| | STORY IN A BUILDING WHERE THE BUILDING IS PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM AND HAS NOT LESS THAN TWO ACCESSIBLE |
| | ROOMS OR SPACES SEPARATED FROM EACH OTHER BY |
| | SMOKE-RESISTING PARTITIONS; OR (2) A SPACE LOCATED IN A |
| | PATH OF TRAVEL LEADING TO A PUBLIC WAY THAT IS |
| | PROTECTED FROM THE EFFECTS OF FIRE, EITHER BY MEANS OF |
| | SEPARATION FROM OTHER SPACES IN THE SAME BUILDING OR BY |
| | VIRTUE OF LOCATION, THEREBY PERMITTING A DELAY IN |
| | EGRESS TRAVEL FROM ANY LEVEL. |
| | 3.3.22.1 ACCESSIBLE AREA OF REFUGE. AN AREA OF REFUGE |
| | THAT COMPLIES WITH THE ACCESSIBLE ROUTE REQUIREMENTS OF |
| | ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR |
| | ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES. |
| | |
| | PER NFPA 1 |
| | |
| | 14.10.4.4 WHERE AN EXIT STAIR IS USED IN AN ACCESSIBLE |
| | MEANS OF EGRESS, IT SHALL COMPLY WITH 7.2.12 OF NFPA |
| | 101 AND EITHER SHALL INCORPORATE AN AREA OF REFUGE |
| | WITHIN AN ENLARGED STORY-LEVEL LANDING OR SHALL BE |
| | ACCESSED FROM AN AREA OF REFUGE. [101:7.5.4.4] |
| | |
| | 7.2.12.1.2 AN AREA OF REFUGE USED AS PART OF A REQUIRED |
| | ACCESSIBLE MEANS OF EGRESS IN ACCORDANCE WITH 7.5.4 IN |
| | OTHER THAN A BUILDING THAT IS PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 9.7 SHALL MEET BOTH OF THE |
| | FOLLOWING CRITERIA: |
| | (1) THE AREA OF REFUGE SHALL MEET THE GENERAL |
| | REQUIREMENTS OF SECTION 7.1. |
| | (2) THE AREA OF REFUGE SHALL MEET THE REQUIREMENTS OF |
| | 7.2.12.2 AND 7.2.12.3. |
| | |
| | 7.2.12.2 ACCESSIBILITY. |
| | 7.2.12.2.1 REQUIRED PORTIONS OF AN AREA OF REFUGE SHALL |
| | BE ACCESSIBLE FROM THE SPACE THEY SERVE BY AN |
| | ACCESSIBLE MEANS OF EGRESS. |
| | 7.2.12.2.2 REQUIRED PORTIONS OF AN AREA OF REFUGE SHALL |
| | HAVE ACCESS TO A PUBLIC WAY VIA AN EXIT OR AN ELEVATOR |
| | WITHOUT REQUIRING RETURN TO THE BUILDING SPACES THROUGH |
| | WHICH TRAVEL TO THE AREA OF REFUGE OCCURRED. |
| | 7.2.12.2.3* WHERE THE EXIT PROVIDING EGRESS FROM AN |
| | AREA OF REFUGE TO A PUBLIC WAY THAT IS IN ACCORDANCE |
| | WITH 7.2.12.2.2 INCLUDES STAIRS, THE CLEAR WIDTH OF |
| | LANDINGS AND STAIR FLIGHTS, MEASURED BETWEEN HANDRAILS |
| | AND AT ALL POINTS BELOW HANDRAIL HEIGHT, SHALL BE NOT |
| | LESS THAN 48 IN. (1220 MM), UNLESS OTHERWISE PERMITTED |
| | BY THE FOLLOWING: |
| | (1) THE MINIMUM 48 IN. (1220 MM) CLEAR WIDTH SHALL NOT |
| | BE REQUIRED WHERE THE AREA OF REFUGE IS SEPARATED FROM |
| | THE REMAINDER OF THE STORY BY A HORIZONTAL EXIT MEETING |
| | THE REQUIREMENTS OF 7.2.4. (SEE ALSO 7.2.12.3.4.) |
| | (2) EXISTING STAIRS AND LANDINGS THAT PROVIDE A CLEAR |
| | WIDTH OF NOT LESS THAN 37 IN. (940 MM), MEASURED AT AND |
| | BELOW HANDRAIL HEIGHT, SHALL BE PERMITTED. |
| | |
| | 7.1.3.2 EXITS. |
| | 7.1.3.2.1 WHERE THIS CODE REQUIRES AN EXIT TO BE |
| | SEPARATED FROM OTHER PARTS OF THE BUILDING, THE |
| | SEPARATING CONSTRUCTION SHALL MEET THE REQUIREMENTS OF |
| | SECTION 8.2 AND THE FOLLOWING: |
| | (1)* THE SEPARATION SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | RESISTANCE RATING WHERE THE EXIT CONNECTS THREE OR |
| | FEWER STORIES. |
| | |
| | 7.2.2 STAIRS. |
| | 7.2.2.1 GENERAL. |
| | 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF |
| | EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF |
| | SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2, |
| | UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2. |
| | |
| | 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS. |
| | 7.2.2.5.1 ENCLOSURES. |
| | 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR |
| | EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| | 7.1.3.2. |
| | |
| | THE PROPOSED STAIRS DO NOT MEET THE REQUIREMENTS TO BE |
| | USED AS AN AREA OF REFUGE AND NOT TO BE USED AS AN |
| | EXIT. |
| | |
| | PLEASE REVIEW AND CLARIFY OR CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE ARE WALLS INDICATED AS P2 BUT NOT |
| | CALL-OUT DIAGRAM. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 4) SHEET A 5 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE |
| | IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE FOR THE APPLICABLE SIGNAGE. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |