| 2017-06-29 17:13:39 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PAGE E.1 |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE OFFICES, |
| | RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND |
| | OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED |
| | BY FLOOR-TO-CEILING HEIGHT PARTITIONS. |
| | THESE AUTOMATIC CONTROL DEVICES SHALL BE INSTALLED TO |
| | AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL |
| | OCCUPANTS LEAVING THE SPACE, |
| | AND SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 |
| | PERCENT POWER |
| | |
| | ASHREA 90.1 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT |
| | LEAST 50% OF ALL 125 VOLT 15- AND 20-AMPERE |
| | RECEPTACLES, INCLUDING THOSE |
| | INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE |
| | FOLLOWING SPACE TYPES: A. PRIVATE OFFICES B. OPEN |
| | OFFICES C. COMPUTER CLASSROOMS |
| | SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT |
| | SHALL FUNCTION ON: A. A SCHEDULED BASIS USING A |
| | TIME-OF-DAY OPERATED CONTROL |
| | DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC |
| | PROGRAMMED TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL |
| | BE PROVIDED FOR AREAS OF NO |
| | MORE THAN 25,000 FT2 BUT NOT MORE THAN ONE FLOOR, OR B. |
| | AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF |
| | WITHIN 30 MINUTES OF ALL |
| | OCCUPANTS LEAVING A SPACE, OR C. A SIGNAL FROM ANOTHER |
| | CONTROL OR ALARM SYSTEM THAT INDICATES THE AREA IS |
| | UNOCCUPIED. EXCEPTIONS: |
| | RECEPTACLES FOR THE FOLLOWING SHALL NOT REQUIRE AN |
| | AUTOMATIC CONTROL DEVICE: A. RECEPTACLES SPECIFICALLY |
| | DESIGNATED FOR EQUIPMENT |
| | REQUIRING 24 HOUR OPERATION. B. SPACES WHERE AN |
| | AUTOMATIC SHUTOFF WOULD ENDANGER THE SAFETY OR SECURITY |
| | OF THE ROOM OR BUILDING |
| | OCCUPANT(S). |
| | |
| | PAGE E.2 |
| | |
| | 250.94 BONDING FOR OTHER SYSTEMS |
| | AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER |
| | SYSTEMS SHALL BE PROVIDED |
| | EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR |
| | METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING |
| | MEANS FOR ANY ADDITIONAL |
| | BUILDINGS OR STRUCTURES. THE INTERSYSTEM B ONDING |
| | TERMINATION SHALL COMPLY WITH THE FOLLOWING: (1) BE |
| | ACCESSIBLE FOR CONNECTION AND INSPECTION. |
| | (2) CONSIST OF A SET OF TERMINALS WITH THE CAPACITY FOR |
| | CONNECTION OF NOT LESS THAN THREE INTERSYSTEM BONDING |
| | CONDUCTORS. (3) NOT INTERFERE |
| | WITH OPENING THE ENCLOSURE FOR A SERVICE, BUILDING OR |
| | STRUCTURE DISCONNECTING MEANS, OR METERING EQUIPMENT. |