Plan Review Notes For Permit 17060134
Permit Number 17060134
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-29 17:13:39CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.1
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES,
 RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND
 OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED
 BY FLOOR-TO-CEILING HEIGHT PARTITIONS.
 THESE AUTOMATIC CONTROL DEVICES SHALL BE INSTALLED TO
 AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL
 OCCUPANTS LEAVING THE SPACE,
 AND SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER
  
 ASHREA 90.1 8.4.2 AUTOMATIC RECEPTACLE CONTROL. AT
 LEAST 50% OF ALL 125 VOLT 15- AND 20-AMPERE
 RECEPTACLES, INCLUDING THOSE
 INSTALLED IN MODULAR PARTITIONS, INSTALLED IN THE
 FOLLOWING SPACE TYPES: A. PRIVATE OFFICES B. OPEN
 OFFICES C. COMPUTER CLASSROOMS
 SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL DEVICE THAT
 SHALL FUNCTION ON: A. A SCHEDULED BASIS USING A
 TIME-OF-DAY OPERATED CONTROL
 DEVICE THAT TURNS RECEPTACLES OFF AT SPECIFIC
 PROGRAMMED TIMES?AN INDEPENDENT PROGRAM SCHEDULE SHALL
 BE PROVIDED FOR AREAS OF NO
 MORE THAN 25,000 FT2 BUT NOT MORE THAN ONE FLOOR, OR B.
 AN OCCUPANT SENSOR THAT SHALL TURN RECEPTACLES OFF
 WITHIN 30 MINUTES OF ALL
 OCCUPANTS LEAVING A SPACE, OR C. A SIGNAL FROM ANOTHER
 CONTROL OR ALARM SYSTEM THAT INDICATES THE AREA IS
 UNOCCUPIED. EXCEPTIONS:
 RECEPTACLES FOR THE FOLLOWING SHALL NOT REQUIRE AN
 AUTOMATIC CONTROL DEVICE: A. RECEPTACLES SPECIFICALLY
 DESIGNATED FOR EQUIPMENT
 REQUIRING 24 HOUR OPERATION. B. SPACES WHERE AN
 AUTOMATIC SHUTOFF WOULD ENDANGER THE SAFETY OR SECURITY
 OF THE ROOM OR BUILDING
 OCCUPANT(S).
  
 PAGE E.2
  
 250.94 BONDING FOR OTHER SYSTEMS
 AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING CONDUCTORS REQUIRED FOR OTHER
 SYSTEMS SHALL BE PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING
 MEANS FOR ANY ADDITIONAL
 BUILDINGS OR STRUCTURES. THE INTERSYSTEM B ONDING
 TERMINATION SHALL COMPLY WITH THE FOLLOWING: (1) BE
 ACCESSIBLE FOR CONNECTION AND INSPECTION.
 (2) CONSIST OF A SET OF TERMINALS WITH THE CAPACITY FOR
 CONNECTION OF NOT LESS THAN THREE INTERSYSTEM BONDING
 CONDUCTORS. (3) NOT INTERFERE
 WITH OPENING THE ENCLOSURE FOR A SERVICE, BUILDING OR
 STRUCTURE DISCONNECTING MEANS, OR METERING EQUIPMENT.