| 2017-06-08 13:43:53 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY THAT SHOWS THE |
| | LOCATION OF THE PROPOSED PERGOLA. FBC 107.2.1 |
| | |
| | 2) PROVIDE TWO SETS OF ELEVATION PLANS. SPECIFY THE |
| | HEIGHT OF THE STRUCTURE ON THE ELEVATION PLANS. |
| | FBC-R301.2.1 |
| | |
| | 3) PROVIDE TWO SETS OF COMPLETE STRUCTURAL DETAILS. |
| | PROVIDE ALL OF THE DIMENSIONS ON THE PLANS INCLUDING |
| | COLUMN SPACING, RAFTER SPACING, ETC. SPECIFY THE |
| | FOUNDATION, THE COLUMNS, THE HEADERS, THE LEDGERS AND |
| | THE RAFTERS ( SIZES AND MATERIALS). SPECIFY ALL OF THE |
| | FASTENERS AND CONNECTORS THAT WILL BE USED TO RESIST |
| | THE WIND LOADS AND PROVIDE A CONTINUOUS LOAD PATH FROM |
| | THE RAFTERS TO THE FOUNDATION. FBC-R301.1 |
| | |
| | 4) SPECIFY THE WIND DESIGN DATA ON THE PLANS. |
| | FBC-R301.2.1 |
| | |
| | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 6) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | |