Plan Review Notes
Plan Review Notes For Permit 17060102
Permit Number 17060102
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-07 10:51:56CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. THE PROJECT ADDRESS ON THE PERMIT APPLICATION IS
 DIFFERENT THAN LISTED ON PLANS. THE ADDRESS AND PARCEL
 NUMBER LISTED ON PERMIT APPLICATION IS FOR A HOOTERS
 RESTAURANT. PLEASE CLARIFY/CORRECT. FBC 107.2.1
 2. INDICATE ON PLANS COMPLIANCE WITH THE REQUIRED
 GROUNDING OF RECEPTACLES AND EQUIPMENT IN PATIENT CARE
 AREAS. NEC 517.13
 3. CONFIRM SIZE OF PANEL A. THE PANEL SCHEDULE STATES
 THAT THIS NEEDS TO BE VERIFIED. PROVIDE CONFIRMATION SO
 THAT DETERMINATION CAN BE MADE THAT THE PANEL SIZE WILL
 BE SUFFICIENT FOR ADDITIONAL LOADS TO BE ADDED. NEC
 408.30, FBC 107.2.1
 4. PROVIDE REQUIRED SHOW WINDOW OUTLETS AND CIRCUIT.
 NEC 210.62
 5. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2
 6. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK. FBC 105.1, 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  