| 2017-06-05 07:19:01 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060101 |
| | ADD: 5050 BROADWAY |
| | CONT: THERMA SEAL ROOFING |
| | TEL: 561-223-2096 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 05/2017 |
| | ACTION: DENIED |
| | |
| | 1) CONTRACTOR SUBMITTED FL2948-R-11 FLORIDA PRODUCT |
| | APPROVAL MODIFIED BITUMEN ROOF SYSTEMS FOR A FLAT ROOF |
| | APPROVAL. THE SUB-SYSTEM THAT WAS IDENTIFIED IS ON PAGE |
| | 5 OF 52 SYSTEM NUMBER W-2. PLEASE NOTE THIS SYSTEM IS |
| | GOOD FOR -45.0 WITH ASTERISK(*) ALLOWING FOR ENHANCED |
| | FASTENING IN ZONES 2 & 3. |
| | |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |