| 2017-06-08 14:05:01 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE FLOOR PLAN. IDENTIFY ALL AREAS OF WORK. |
| | DESIGNER TO PRINT NAME AND SIGN PLAN. |
| | 2. PROVIDE TYPE OF UNDERLAYMENT TO BE USED FOR |
| | FLOORING. |
| | 3. PROVIDE THE FOLLOWING ASTM'S FOR THE PROPOSED |
| | UNDERLAYMENT - ASTM E-84 (FLAME SPREAD, LAMINATE ONLY), |
| | ASTM E-90 (AIRBOURNE SOUND) & ASTM E-492 (IMPACT |
| | SOUND). |
| | 4. PLUMBING PERMIT REQUIRED. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE |
| | THEIR PRINTED NAME AND SIGNATURE ON THE SUBMITTED PLANS |
| | AND SUPPORTING DOCUMENTS PER FBC 107. |
| | |
| | FBC 603.1 FLAME SPREAD ? ASTM E-84 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |