| Plan Review Notes For Permit 17060078 |
| Permit Number |
17060078 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-05 12:32:31 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED CUT SHEETS FOR THE EQUIPMENT SHOWING LISTINGS. | | | 110.3 NEC 2011 PRIOR TO THE INSTALLATION OF THE | | | EQUIPMENT. | | | | | | ONE NOTE ON SERVICE MAIN STATED IF NOT INTERGRAL WITH | | | THE EQUIPMENT SUPPLY DISCONNECT. | | | IF INTERGRAL WITH THE EQUIPMENT THEN THE DISCONNECT | | | WOULD HAVE TO BE SERVICE ENTERANCE RATED | | | 230.66 NEC 2011 | | | | | | THE GROUNDING ELECTRODE CONDUCTOR SHOWS ALUMINUM WIRE | | | IT IS NOT ALLOWED TO CONNECT TO THE GROUND ROD OR BE | | | WITHIN 18" OF EARTH. 250.64 (A) |
|