Plan Review Notes
Plan Review Notes For Permit 17060078
Permit Number 17060078
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-05 12:32:31CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED CUT SHEETS FOR THE EQUIPMENT SHOWING LISTINGS.
 110.3 NEC 2011 PRIOR TO THE INSTALLATION OF THE
 EQUIPMENT.
  
 ONE NOTE ON SERVICE MAIN STATED IF NOT INTERGRAL WITH
 THE EQUIPMENT SUPPLY DISCONNECT.
 IF INTERGRAL WITH THE EQUIPMENT THEN THE DISCONNECT
 WOULD HAVE TO BE SERVICE ENTERANCE RATED
 230.66 NEC 2011
  
 THE GROUNDING ELECTRODE CONDUCTOR SHOWS ALUMINUM WIRE
 IT IS NOT ALLOWED TO CONNECT TO THE GROUND ROD OR BE
 WITHIN 18" OF EARTH. 250.64 (A)