| Plan Review Notes For Permit 17060070 |
| Permit Number |
17060070 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-02 14:15:14 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. BASE FLOOD ELEVATION IS 7.0 FEET. ATTACHED GARAGE | | | (TOP OF SLAB) IS 6.0 FEET. FLOOD OPENINGS REQUIRED. | | | 1A. ENGINEERED FLOOD OPENINGS - PROVIDE CERTIFICATION | | | BY A FLORIDA REGISTERED DESIGN PROFESSIONAL OR AN | | | EVALUATION REPORT FROM THE INTERNATIONAL CODE COUNCIL | | | (ICC). | | | 1B. NON-ENGINEERED FLOOD OPENINGS - PROVIDE DESIGN WITH | | | DEMENSIONS TO VERIFY THE PRESCRIPTIVE REQUIREMENTS OF 1 | | | SQ. INCH OF NET OPENING PER 1 SQ. FOOT OF ENCLOSED | | | AREA. | | | 2. ALL SUBMITTAL DOCUMENTS SHALL BE IN DUPLICATE. |
|