Plan Review Notes
Plan Review Notes For Permit 17060065
Permit Number 17060065
Review Stop M
Sequence Number 2
Notes
Date Text
2017-11-02 12:19:192ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17060065
 11/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 IT APPEARS THAT ONLY ONE UPDATED SET OF MECHANICAL
 PLANS WAS SUBMITTED IN THE CORRECTED PLAN SETS. THAT
 REVISED SET HAS THE ENGINEER'S SEAL DATED 10/6/17
 AFFIXED. I HAVE REVIEWED THAT SET ALONG WITH THE
 SUBMITTED NARRATIVE RESPONSE TO 1ST REVIEW COMMENTS
 FROM HUNTONBRADY AND HAVE FOUND DEFIICENCIES. PLEASE
 REFER TO 1ST REVIEW COMMENTS WHICH I HAVE ITEMIZED
 BELOW.
  
 COMMENT #1: COMMISSIONING PLAN NOT PROVIDED.
  
 #2) SMOKE DETECTORS NOT SHOWN ON SHEET M111 AS
 INDICATED IN THE NARRATIVE.
  
 #3) MATERIALS TO BE STORED IN DIS-PREP STORAGE ROOM NOT
 IDENTIFIED, AND STORAGE EXHAUST NOT PROVIDED AS
 INDICATED IN THE NARRATIVE.
  
 #4) THE ROOFTOP MECHANICAL EQUIPMENT CURB AND BASE
 ATTACHMENTS TO THE ROOF STRUCTURE HAVE NOT BEEN
 PROVIDED FOR THE ROOF UPBLAST FAN, AND THE ISOLATION
 ROOM FAN. PLEASE CLARIFY IF THE ISOLATION ROOM AND THE
 DECON ROOM ARE ONE IN THE SAME, OR IF THERE IS A ROOM
 DESIGNATED AS ISOLATION ROOM SOMEWHERE ELSE ON THE
 PLAN- I CANNOT LOCATE IT.
  
 #5) PLEASE ADD OUTDOOR AHU SOUND LEVEL NOTE TO THE
 PLANS.
  
 #6) NOTE #20 ON THE REVISED SHEET M121 IS NOT ON THE
 PLAN AS INDICATED IN THE NARRATIVE.
  
 #8) THE DESIGN PARAMETER TABLE SHOWING THE ROOM-TO-ROOM
 PRESSURE RELATIONSHIPS ON SHEET M111 HAS NOT BEEN
 PROVIDED AS INDICATED IN THE NARRATIVE.
  
 #9) THE REVISED ENERGY COMPLIANCE FORM SHOWING THE
 WATER HEATER AND PIPING SYSTEM COMPLIANCE DATA HAS NOT
 BEEN PROVIDED.
  
 1) NEW COMMENT: REFER TO SECTION 449.3.6.5 FBC-14
 BUILDING AS IT APPLIES TIO THE NEW TRAUMA CENTER. IT
 APPEARS THAT VARIABLE-AIR VOLUME SYSTEMS MAY NOT BE
 PERMITTED FOR USE IN THE DECON ROOM AND POSSIBLY THE
 TRAUMA ROOMS- PLEASE CLARIFY THE USE OF THESE ROOMS
 WHAT PROCEDURES ARE PERFOMED IN EACH.
  
 2) NEW COMMENT: PROVIDE PRODUCT DATA FOR THE DUCTWORK
 IN THE TRAUMA ROOM ON THE PLANS, AND PROVIDE A
 SUBMITTAL REVIEWED BY THE DESIGN PROFESSIONALS OF
 RECORD.
  
 3) NEW COMMENT: PLEASE REVIEW SECTION 2.1-8.2.4.3(2) IN
 THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH
 CARE FACILITIES. IT APPEARS THAT ANESTHESIA SCAVENGING
 SYSTEMS NEED TO BE INSTALLED IN THE TRAUMA ROOMS.
 PLEASE COMPLY.
  
 4) NEW COMMENT: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE EXHAUST DUCT WRAP. PLEASE CLARIFY WHAT FUMES OR
 GASES ARE BEING EXHAUSTED FROM THE ROOM AND WHY THE
 EXHAUST DUCT NEEDS TO BE WRAPPED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved