| Date |
Text |
| 2017-11-02 12:19:19 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060065 |
| | 11/2/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | IT APPEARS THAT ONLY ONE UPDATED SET OF MECHANICAL |
| | PLANS WAS SUBMITTED IN THE CORRECTED PLAN SETS. THAT |
| | REVISED SET HAS THE ENGINEER'S SEAL DATED 10/6/17 |
| | AFFIXED. I HAVE REVIEWED THAT SET ALONG WITH THE |
| | SUBMITTED NARRATIVE RESPONSE TO 1ST REVIEW COMMENTS |
| | FROM HUNTONBRADY AND HAVE FOUND DEFIICENCIES. PLEASE |
| | REFER TO 1ST REVIEW COMMENTS WHICH I HAVE ITEMIZED |
| | BELOW. |
| | |
| | COMMENT #1: COMMISSIONING PLAN NOT PROVIDED. |
| | |
| | #2) SMOKE DETECTORS NOT SHOWN ON SHEET M111 AS |
| | INDICATED IN THE NARRATIVE. |
| | |
| | #3) MATERIALS TO BE STORED IN DIS-PREP STORAGE ROOM NOT |
| | IDENTIFIED, AND STORAGE EXHAUST NOT PROVIDED AS |
| | INDICATED IN THE NARRATIVE. |
| | |
| | #4) THE ROOFTOP MECHANICAL EQUIPMENT CURB AND BASE |
| | ATTACHMENTS TO THE ROOF STRUCTURE HAVE NOT BEEN |
| | PROVIDED FOR THE ROOF UPBLAST FAN, AND THE ISOLATION |
| | ROOM FAN. PLEASE CLARIFY IF THE ISOLATION ROOM AND THE |
| | DECON ROOM ARE ONE IN THE SAME, OR IF THERE IS A ROOM |
| | DESIGNATED AS ISOLATION ROOM SOMEWHERE ELSE ON THE |
| | PLAN- I CANNOT LOCATE IT. |
| | |
| | #5) PLEASE ADD OUTDOOR AHU SOUND LEVEL NOTE TO THE |
| | PLANS. |
| | |
| | #6) NOTE #20 ON THE REVISED SHEET M121 IS NOT ON THE |
| | PLAN AS INDICATED IN THE NARRATIVE. |
| | |
| | #8) THE DESIGN PARAMETER TABLE SHOWING THE ROOM-TO-ROOM |
| | PRESSURE RELATIONSHIPS ON SHEET M111 HAS NOT BEEN |
| | PROVIDED AS INDICATED IN THE NARRATIVE. |
| | |
| | #9) THE REVISED ENERGY COMPLIANCE FORM SHOWING THE |
| | WATER HEATER AND PIPING SYSTEM COMPLIANCE DATA HAS NOT |
| | BEEN PROVIDED. |
| | |
| | 1) NEW COMMENT: REFER TO SECTION 449.3.6.5 FBC-14 |
| | BUILDING AS IT APPLIES TIO THE NEW TRAUMA CENTER. IT |
| | APPEARS THAT VARIABLE-AIR VOLUME SYSTEMS MAY NOT BE |
| | PERMITTED FOR USE IN THE DECON ROOM AND POSSIBLY THE |
| | TRAUMA ROOMS- PLEASE CLARIFY THE USE OF THESE ROOMS |
| | WHAT PROCEDURES ARE PERFOMED IN EACH. |
| | |
| | 2) NEW COMMENT: PROVIDE PRODUCT DATA FOR THE DUCTWORK |
| | IN THE TRAUMA ROOM ON THE PLANS, AND PROVIDE A |
| | SUBMITTAL REVIEWED BY THE DESIGN PROFESSIONALS OF |
| | RECORD. |
| | |
| | 3) NEW COMMENT: PLEASE REVIEW SECTION 2.1-8.2.4.3(2) IN |
| | THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH |
| | CARE FACILITIES. IT APPEARS THAT ANESTHESIA SCAVENGING |
| | SYSTEMS NEED TO BE INSTALLED IN THE TRAUMA ROOMS. |
| | PLEASE COMPLY. |
| | |
| | 4) NEW COMMENT: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE EXHAUST DUCT WRAP. PLEASE CLARIFY WHAT FUMES OR |
| | GASES ARE BEING EXHAUSTED FROM THE ROOM AND WHY THE |
| | EXHAUST DUCT NEEDS TO BE WRAPPED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |