2017-10-26 08:56:512014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060065
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. OCT. 26/2017
 ACTION: DENIED
  
  
 PLANS APPEAR TO BE CODE COMPLIANT, STAMPED NEED
 RESIDENT INSPECTOR FORMS TO PASS INTHE COMPUTER
 PROGRAM>
 10/26/2017
  
  
 1) COMPLIED.
  
 2) BUILDING PROVISO / DEFERRED SUBMITTALS: SHEET S121
 CONSTRUCTION NOTE NUMBER 1 INDICATES THE ARCHITECTURAL
 ALUMINUM CANOPY DECK, SOFFIT AND FASCIA ARE
 PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF RECORD
 FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL BEFORE BEING
 FORWARDED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2ND REVIEW. THE CONTRACTOR ELECTS TO USE A RESIDENT
 INSPECTOR FORMS WILL BE E-MAILED TO:
 [email protected] SENT 10/25/2017 04:28 PM.
  
 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW MAY BE SCHEDULED.
  
 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3E) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 AND
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 RESIDENT INSPECTORS. COMMENT # 14. 3 COPIES OF ALL SHOP
 DRAWINGS (HANDRAILS, PRECAST JOINT AND SLABS, PRODUCT
 APPROVALS, TRUSSES, BAR JOIST, ETC.) MUST BE SUBMITTED
 TO THE BUILDING DEPARTMENT. TWO REVIEWED SETS OF
 DOCUMENTS WILL BE RETURNED TO THE JOB SITE BEFORE ANY
 OF THE ABOVE ARE INSTALLED ON THE JOB.
  
 3F) INFORMATION ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 4)BUILDING PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 SUBMITTED PRODUCT APPROVALS:
 FL 12400.3 FLUSH OUTSWING DOOR
 FL20701-R1 SWINGING EXTERIOR DOOR
 FL 16392-R2 1006 SERIES ELECTRIC STRIKE
 FL 14313-R5 CURTAIN WALL
 NOA 15-0226.03 STO THERM CI LM 180 CMU EFIS SYSTEM
  
 5) BUILDING PROVISO / DEFERRED SUBMITTAL: FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) BUILDING PROVISO / DEFERRED SUBMITTAL: ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) BUILDING PROVISO / DEFERRED SUBMITTAL / DELEGATE
 SESIGN ) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE
 DOWN NOTE:
 ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014
 AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT
 LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL
 ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE
 STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER