Plan Review Notes
Plan Review Notes For Permit 17060065
Permit Number 17060065
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-28 13:41:541ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE RELOCATED VENT TERMINAL NEXT TO NEW MECHANICAL
 RM TG326 SHALL COMPLY-WITH FBC PL 903.5 LOCATION OF
 VENT TERMINAL.
 AN OPEN VENT TERMINAL FROM A DRAINAGE SYSTEM SHALL NOT
 BE LOCATED DIRECTLY BENEATH ANY DOOR, OPENABLE WINDOW,
 OR OTHER AIR INTAKE OPENING OF THE BUILDING OR OF AN
 ADJACENT BUILDING, AND ANY SUCH VENT TERMINAL SHALL NOT
 BE WITHIN 10 FEET (3048 MM) HORIZONTALLY OF SUCH AN
 OPENING UNLESS IT IS 3 FEET (914 MM) OR MORE ABOVE THE
 TOP OF SUCH OPENING.
  
 903.6 EXTENSION THROUGH THE WALL.
 VENT TERMINALS EXTENDING THROUGH THE WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM)
 FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM)
 ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT
 TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT
 VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO
 PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE
 VENT OPENING.
  
 2. HOLDING TANK FOR DECON SHOWER.
 A) HOW WILL THIS TANK BE EMPTIED OUT AND WHEN WILL THE
 TANK BE EMPTIED.
 B) PLEASE PROVIDE MANUFACTURE SPECIFICATION ON THE TANK
 AND WATER LEVEL SENSOR.
 C) WHAT TYPE OF CHEMICALS COULD BE INTRODUCED INTO THE
 TANK.
 PER WPB AMEND TP FBC 107.2.1
  
 3. PLEASE PROVIDE TRAP PRIMER FOR THE FLOOR DRAIN IN
 THE DECON SHOWER. PER FBC PL 1002.4
  
 4, PLEASE PROVIDE A MEDICAL GAS RISER. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 TEMPERED WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
  
 6. LABEL FIXTURES ON RISER FOR BATHROOM TG337. PER WPB
 AMEND TP FBC 107.2.1
  
 7. THE BRANCH DRAIN FOR THE BREAKROOM SINK SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP
 TG337. PER FBC PL 912.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH