Plan Review Notes
Plan Review Notes For Permit 17060065
Permit Number 17060065
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-28 17:26:151ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #17060065
 6/28/17
  
 PLAN REVIEW RESULT: DENIED
  
 1) PROVIDE A COMMISSIONING PLAN- SECTION C408.2.1
 FBC-14 ENERGY CONSERVATION.
  
 2) SHOW THE LOCATIONS OF THE REQUIRED SMOKE DETECTORS
 IN THE RETURN AIR SYSTEMS OF AHU-G-1 & G-2- SECTION
 606.2.1.
  
 3) INDICATE WHAT MATERIALS ARE BEING STORED IN THE DIS
 PREP STOR ROOM TG322. WILL MEDICAL GAS BE STORED IN THE
 ROOM OR ANY OTHER NEW ROOMS OR SPACES? PLEASE NOTE A
 LOCAL EXHAUST SYSTEM MAY BE REQUIRED.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 ALL THE ROOFTOP MECHANICAL EQUIPMENT INCLUDING THE
 AHU'S AND CURBS, THE EF'S AND CURBS, THE DUCTWORK AND
 SUPPORT BRACKETS- SECTION 301.15.
  
 5) PROVIDE THE ANTICIPATED DBA LEVEL OF THE NEW ROOFTOP
 AHU'S AND FANS IN ACCORDANCE WITH SECTION
 2.1-8.2.1.1(6)(A) GUIDELINES FOR DESIGN AND
 CONSTRUCTION OF HEALTH CARE FACILITIES.
  
 6) INDICATE THE HEIGHT OF THE AHU AIR INLETS ABOVE THE
 ROOF LEVEL- SEE SECTION 6-3.1 ASHRAE 170.
  
 7) PROVIDE SPECIFICATIONS FOR THE ROOF TOP DUCTWORK AND
 INSULATION, AND THE CHILLED AND STEAM WATER PIPING AND
 INSULATIONS.
  
 8) PLEASE INCLUDE THE PRESSURE RELATIONSHIPS, AND
 EXHAUST AND RECIRCULATION PARAMETERS FOR ALL ROOMS AND
 SPACES IN THE ASHRAE 170, 62.1 CALCULATION SUBMITTAL.
 IT MAY BE HELPFUL TO PLACE THE TABLES ON THE MECHANICAL
 PLANS.
  
 9) PROVIDE THE WATER HEATER AND PIPING SYSTEM
 COMPLIANCE DATA IN THE ENERGYGAUGE SUBMITTAL.
  