| 2017-06-28 17:26:15 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #17060065 |
| | 6/28/17 |
| | |
| | PLAN REVIEW RESULT: DENIED |
| | |
| | 1) PROVIDE A COMMISSIONING PLAN- SECTION C408.2.1 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) SHOW THE LOCATIONS OF THE REQUIRED SMOKE DETECTORS |
| | IN THE RETURN AIR SYSTEMS OF AHU-G-1 & G-2- SECTION |
| | 606.2.1. |
| | |
| | 3) INDICATE WHAT MATERIALS ARE BEING STORED IN THE DIS |
| | PREP STOR ROOM TG322. WILL MEDICAL GAS BE STORED IN THE |
| | ROOM OR ANY OTHER NEW ROOMS OR SPACES? PLEASE NOTE A |
| | LOCAL EXHAUST SYSTEM MAY BE REQUIRED. |
| | |
| | 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | ALL THE ROOFTOP MECHANICAL EQUIPMENT INCLUDING THE |
| | AHU'S AND CURBS, THE EF'S AND CURBS, THE DUCTWORK AND |
| | SUPPORT BRACKETS- SECTION 301.15. |
| | |
| | 5) PROVIDE THE ANTICIPATED DBA LEVEL OF THE NEW ROOFTOP |
| | AHU'S AND FANS IN ACCORDANCE WITH SECTION |
| | 2.1-8.2.1.1(6)(A) GUIDELINES FOR DESIGN AND |
| | CONSTRUCTION OF HEALTH CARE FACILITIES. |
| | |
| | 6) INDICATE THE HEIGHT OF THE AHU AIR INLETS ABOVE THE |
| | ROOF LEVEL- SEE SECTION 6-3.1 ASHRAE 170. |
| | |
| | 7) PROVIDE SPECIFICATIONS FOR THE ROOF TOP DUCTWORK AND |
| | INSULATION, AND THE CHILLED AND STEAM WATER PIPING AND |
| | INSULATIONS. |
| | |
| | 8) PLEASE INCLUDE THE PRESSURE RELATIONSHIPS, AND |
| | EXHAUST AND RECIRCULATION PARAMETERS FOR ALL ROOMS AND |
| | SPACES IN THE ASHRAE 170, 62.1 CALCULATION SUBMITTAL. |
| | IT MAY BE HELPFUL TO PLACE THE TABLES ON THE MECHANICAL |
| | PLANS. |
| | |
| | 9) PROVIDE THE WATER HEATER AND PIPING SYSTEM |
| | COMPLIANCE DATA IN THE ENERGYGAUGE SUBMITTAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |