| 2017-06-08 10:11:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G 109 - THE LIFE SAFETY PLAN DOES NOT APPEAR |
| | TO INDICATED EXIT CONDITIONS DURING CONSTRUCTION. THE |
| | LIFE SAFETY PLAN MUST INDICATE HOW THE CONSTRUCTION |
| | AREA WILL BE PROTECTED/SEPARATED FROM REGULAR BUSINESS |
| | ACTIVITIES. |
| | |
| | WHAT EXITS WILL BE BLOCKED, HOW WILL THEY REROUTE |
| | PEOPLE, WHAT IS/ARE THE PROPOSED OCCUPANCY LOADS |
| | CHANGING BASED ON THE REROUTING, WILL FIRE ALARM |
| | DEVICES/NOTIFICATIONS BE AFFECTED BY THE CONSTRUCTION |
| | SEPARATIONS , NEW EXIT SIGNS, NEW EMERGENCY LIGHTING, |
| | ETC. |
| | |
| | PLEASE PROVIDE DETAILED INDICATIONS AND NARRATIVES |
| | RELATING TO THE ABOVE. |
| | |
| | |
| | |
| | 2) SHEET G 109 - THERE IS A NOTE INDICATING EXISTING DE |
| | DOORS WILL BE REMOVED AT THE END OF PHASE 1A. HAVE |
| | THESE DOORS BEEN ELVALUATED FOR THEIR FUNCTION RELATING |
| | TO SMOKE CONTROL/BARRIERS? |
| | |
| | PLEASE REVIEW THE EXISTING LIFE SAFETY ENGINEERING |
| | SYSTEMS AND ENSURE THAT THESE DOORS CAN BE REMOVED AND |
| | PROVIDE AND APPLICATION NOTE OR LETTE FROM THE EOR. |
| | |
| | |
| | |
| | |
| | 3) LIFE SAFETY SHEETS - IN ADDITION TO THE ABOVE |
| | COMMENT, DOES ANY OF THE PROPOSED CONSTRUCTION PHASES |
| | INTERFERE WITH THE EXISTING ENGINEERED LIFE SAFETY |
| | EQUIPMENT/FEATURES OF THE OCCUPANCY. |
| | |
| | IS THERE SMOKE CONTROL, SMOKE BARRIERS, |
| | PRESSURIZATIONS, EVACUATION SYSTEMS THAT MAY OR WILL BE |
| | COMPROMISED BY THIE PROPOSED CONSTRUCTION? |
| | |
| | PLEASE PROVIDE A DETAILED REVIEW OF ALL PHASES AND/OR |
| | PROVIDE FOR THE CORRECTION OR MAINTENANCE OF THESE |
| | SYSTEMS. |
| | |
| | |
| | |
| | |
| | 4) F 111.A - THE FFP PAGE TITLE SHOWS ONLY PHASE 1 - A; |
| | HOWEVER, ALL PHASES APPEAR TO BE DRAWN. |
| | |
| | EACH PHASE SHOULD BE DETAILED ON HOW IT WILL BE |
| | ISOLATED OR CONTROLLED TO MAINTAIN FUNCTION THROUGHOUT |
| | CONTRUCTION. |
| | |
| | PLEASE REVIEW, CLARIFY OR CORRECT. |
| | |
| | |
| | |
| | |
| | 5) SHEET E 001 - UNDER DEMOLITION GENERAL NOTES AND |
| | GENERAL NOTES, THERE IS/ARE NO INDICATIONS OF FIRE |
| | ALARM WORK. THE FIRE ALARM SHALL BE MAINTAINED |
| | THROUGHOUT CONTRUCTION. ALL WORK SHALL BE DONE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS UNDER SEPARATE SHOP |
| | DRAWINGS. BASED ON THE SEPARATION OF AREAS AND PHASES, |
| | ADDITIONAL DEVICES MAY BE REQUIRED FOR CODE COVERAGE |
| | PURPOSES. |
| | |
| | PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE. |
| | |
| | |
| | |
| | 6) SHEET E 109 - THERE ARE TWO NOTE TAGE; 0.99.1 & |
| | 0.98.1, THAT DO NOT APPEAR TO HAVE AN OBVIOUS |
| | EXPLANATION DETAIL OF DEFINITION. WHAT DOES THESE |
| | INDICATE. |
| | |
| | PLEASE CLARIFY. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |