Plan Review Notes
Plan Review Notes For Permit 17060065
Permit Number 17060065
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-27 10:45:53CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. THE DEMAND AMPS/KVA FOR PANEL EGLB1 EXCEED THE
 CAPACITY OF TRANSFORMER T-EGLB1. PROVIDE CORRECTION.
 NEC 517.30(D); 230.79
 2. PROVIDE PANEL SCHEDULE FOR PANEL QDP-B. NEC 408.4;
 215.5; FBC 107.2.1
 3. SHEET E802, PANEL TDP1, LOAD CALCULATION PROVIDED
 SHOWS X-RAY LOAD WITH A 19.17% DEMAND FACTOR, AND
 RECEPTACLE LOAD WITH A 78.41% DEMAND FACTOR. PROVIDE
 CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS
 ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220;
 FBC 107.2.1
 4. SHEET E805, PANEL XRH, LOAD CALCULATION PROVIDED
 SHOWS X-RAY LOAD WITH A 37.5% DEMAND FACTOR. PROVIDE
 CODE SECTION FROM THE NEC WHERE THESE DEMAND FACTORS
 ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220;
 FBC 107.2.1
 5. SEVERAL PANEL SCHEDULES SHOW THE LIGHTING DEMAND
 FACTOR AT 40% (EXAMPLE PANEL CGHC2 AND GHC2). THE NOTE
 AT THE BOTTOM OF TABLE 220.42 STATES THAT THIS DEMAND
 FACTOR SHOULD NOT BE USED WHERE IT IS LIKELY THE
 LIGHTING WILL BE ON AT THE SAME TIME, SUCH AS THE
 TRAUMA ROOMS. PROVIDE CLARIFICATION FOR THIS DEMAND
 FACTOR, INDICATING ANY AREAS WHERE LIGHTING WILL BE
 USED AT THE SAME TIME. FBC 107.2.1; NEC TABLE 220.42
 6. SHEET E801 AND E802, ISOLATION PANELS T1A, T1B, T2A,
 T2B, T3A, T3B, T4A, T4B: NOTE STATES THAT THE BRANCH
 CIRCUITS WILL BE ON A 2 POLE BREAKER, BUT THIS IS NOT
 REFLECTED IN THE PANEL SCHEDULE. PROVIDE CORRECTION TO
 ACCURATELY REFLECT THE PANEL LAYOUT. FBC 107.2.1; NEC
 408.4
 7. SHEET E803, PANEL EQH1, LOAD CALCULATION PROVIDED
 SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, AND
 THE COOLING LOAD WITH A 85% DEMAND FACTOR. PROVIDE CODE
 SECTION FROM THE NEC WHERE THESE DEMAND FACTORS ARE
 LOCATED AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC
 107.2.1
 8. SHEET E803, PANEL EQL1, LOAD CALCULATION PROVIDED
 SHOWS THE COOLING LOAD WITH A 85% DEMAND FACTOR.
 PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND
 FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS.
 NEC 220; FBC 107.2.1
 9. SHEET E804, PANEL TMSB, LOAD CALCULATION PROVIDED
 SHOWS THE RECEPTACLE LOAD WITH A 51.04% DEMAND FACTOR,
 THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE
 COOLING LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY
 LOAD WITH A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION
 FROM THE NEC WHERE THESE DEMAND FACTORS ARE LOCATED
 AND/OR CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1
 10. SHEET E804, PANEL TESB, LOAD CALCULATION PROVIDED
 SHOWS RECEPTACLE LOAD WITH A 51.06% DEMAND FACTOR, THE
 MOTOR LOAD WITH A 118.49% DEMAND FACTOR, THE COOLING
 LOAD WITH A 85% DEMAND FACTOR, AND THE X-RAY LOAD WITH
 A 19.17% DEMAND FACTOR. PROVIDE CODE SECTION FROM THE
 NEC WHERE THESE DEMAND FACTORS ARE LOCATED AND/OR
 CORRECT THE DEMAND FACTORS. NEC 220; FBC 107.2.1
 11. WITH THE CURRENT LOAD CALCULATION PROVIDED, IT
 APPEARS GENERATOR #1 IS OVERLOADED. PANEL TESB SHOWS A
 DEMAND OF 1027.3 KVA AND THE GENERATOR IS RATED FOR
 1000. IF ANY CORRECTIONS TO LOAD CALCULATIONS FROM
 ABOVE COMMENTS RESULT IN ADDITIONAL LOAD, THEN THIS
 WILL INCREASE THE OVERLOAD. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1, NEC 517.30(D)
 12. SHEET E804, PANEL QDP, LOAD CALCULATION PROVIDED
 SHOWS THE MOTOR LOAD WITH A 118.49% DEMAND FACTOR.
 PROVIDE CODE SECTION FROM THE NEC WHERE THESE DEMAND
 FACTORS ARE LOCATED AND/OR CORRECT THE DEMAND FACTORS.
 NEC 220; FBC 107.2.1
 13. PROVIDE AUTOMATIC LIGHTING CONTROLS FOR INTERIOR
 LIGHTING PER THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION. FBC C401.2.1, C405
 14. SHEET E901, LIGHTING CONTACTOR DETAIL SHOWS A
 PHOTOCELL CONTROLLING THE CONTACTOR. ENERGY CODE
 STATES: "EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS". PROVIDE
 CORRECTION. FBC C405.2.4
 15. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2
 16. INDICATE PANEL BOARD BONDING REQUIRED. NEC 517.14
 17. SHEETS V106, V206, V306, V406, V506, V606: INDICATE
 WHICH MODEL IS USED TO DETERMINE PROPER WIRING
 REQUIREMENTS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  