2017-06-27 16:31:262014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060065
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 27/2017
 ACTION: DENIED
  
 1) THE PLANS INDICATE NEW ADDITIONS TO THE HOSPITAL BUT
 THERE WAS NO SOILS REPORT SUBMITTED THIS REVIEW. 2014
 FBC-B 803.5.2 QUESTIONABLE SOIL.
  
 2) SHEET S121 CONSTRUCTION NOTE NUMBER 1 INDICATES THE
 ARCHITECTURAL ALUMINUM CANOPY DECK, SOFFIT AND FASCIA
 ARE PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF
 RECORD FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL
 BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) THE CANOPY, NEW X-RAY, RADIATION ROOMS, OFFICES AND
 TRAUMA UNIT ADDITIONS SHOW STEEL BEAMS & BOLTED
 CONNECTIONS OR WELDED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 IF THE CONTRACTOR PREFERS THE USE OF A RESIDENT
 INSPECTOR FOR THE EFFICIENCY OF THE JOB, PLEASE PROVIDE
 DOCUMENTATION IN THE COMMENT RESPONSE NARRATIVE. THIS
 WILL REQUIRE RESIDENT INSPECTORS FORMS, AND ALSO 3 SETS
 OF PLANS.
  
 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
 IF THE CONTRACTOR WISHES TO DEFER THE PRODUCT APPROVALS
 UNTIL AFTER PERMIT ISSUANCE PLEASE INFORM THROUGH THE
 COMMENT RESPONSE.
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 8) SHEET A201, A231, A241 & A242 ALL SHOW THE
 INSTALLATION OF EFIS SYSTEMS. : PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED. PLEASE
 ALSO PROVIDE THE MANUFACTURERS INSTALLATION BROCHURE
 PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 9) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE DOWN
 NOTE:
 ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014
 AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT
 LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL
 ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE
 STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA,
 PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS.
  
  
 10) SHEET A811 DETAIL A10 DETAILS TO X-RAY ROOMS AND
 CONTROL ROOM AS WELL AS IN THE 4 TRAUMA UNITS.
 . FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL
 HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS
 NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A
 RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN
 PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE.
 PLEASE SHOW COMPLIANCE WITH:
 10A) FBC-B 465.5.1.1 STRUCTURAL SHIELDING IN WALLS AND
 OTHER VERTICAL BARRIERS REQUIRED FOR PERSONNEL
 PROTECTION SHALL EXTEND WITHOUT BREACH FROM THE FLOOR
 TO A HEIGHT OF AT LEAST 7 FEET (2.1 M).
  
 10B) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND
 WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT
 SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER
 IN WHICH THEY ARE INSTALLED.
  
 10C) FBC-B 465.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR
 PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 10D) 465.5.1.3.1 THE PLANS SHALL SHOW, AS A MINIMUM,
 THE FOLLOWING.
  
 465.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM'S
 RADIATION PORT; THE PORT'S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR'S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
  
 465.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED.
  
 465.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED.
  
 465.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT
 AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM
 CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE
 TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS
 MAY BE PRESENT.
  
 465.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
  
 465.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
  
 10E) 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  