| 2017-06-27 16:31:26 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060065 |
| | ADD: 901 45TH ST. |
| | CONT: WESTBROOKE CORP |
| | TEL: 561-395-4126 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 27/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS INDICATE NEW ADDITIONS TO THE HOSPITAL BUT |
| | THERE WAS NO SOILS REPORT SUBMITTED THIS REVIEW. 2014 |
| | FBC-B 803.5.2 QUESTIONABLE SOIL. |
| | |
| | 2) SHEET S121 CONSTRUCTION NOTE NUMBER 1 INDICATES THE |
| | ARCHITECTURAL ALUMINUM CANOPY DECK, SOFFIT AND FASCIA |
| | ARE PRE-ENGINEERED. PLEASE SUBMIT TO THE DESIGNER OF |
| | RECORD FOR REVIEW, SHOP DRAWING STAMP OF APPROVAL |
| | BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) THE CANOPY, NEW X-RAY, RADIATION ROOMS, OFFICES AND |
| | TRAUMA UNIT ADDITIONS SHOW STEEL BEAMS & BOLTED |
| | CONNECTIONS OR WELDED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | IF THE CONTRACTOR PREFERS THE USE OF A RESIDENT |
| | INSPECTOR FOR THE EFFICIENCY OF THE JOB, PLEASE PROVIDE |
| | DOCUMENTATION IN THE COMMENT RESPONSE NARRATIVE. THIS |
| | WILL REQUIRE RESIDENT INSPECTORS FORMS, AND ALSO 3 SETS |
| | OF PLANS. |
| | |
| | 4) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS, ROOF TOP INTAKE AND EXHAUST FANS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | IF THE CONTRACTOR WISHES TO DEFER THE PRODUCT APPROVALS |
| | UNTIL AFTER PERMIT ISSUANCE PLEASE INFORM THROUGH THE |
| | COMMENT RESPONSE. |
| | |
| | 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 8) SHEET A201, A231, A241 & A242 ALL SHOW THE |
| | INSTALLATION OF EFIS SYSTEMS. : PLEASE PROVIDE THE |
| | PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED. PLEASE |
| | ALSO PROVIDE THE MANUFACTURERS INSTALLATION BROCHURE |
| | PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.3 STRUCTURAL DESIGN. |
| | 1408.4 WEATHER RESISTANCE. |
| | 1408.4.1 EIFS WITH DRAINAGE. |
| | 408.4.1.1 WATER-RESISTIVE BARRIER. |
| | 1408.5 INSTALLATION. |
| | |
| | 9) SHEET M301 ROOF TOP CURB AND EQUIPMENT TIE DOWN |
| | NOTE: |
| | ALL SUPPORTS SHALL BE IN COMPLIANCE WITH FBC/FMC 2014 |
| | AND THE HURRICANE CODES TO WITHSTAND WIND AND IMPACT |
| | LOADS AND DESIGNED BY A FLORIDA REGISTERED STRUCTURAL |
| | ENGINEER. SUBMIT CALCULATIONS FOR REVIEW. SEE |
| | STRUCTURAL DRAWINGS FOR THE WIND DESIGN CRITERIA, |
| | PLEASE PROVIDE. 107.2.1.3 ADDITIONAL INFORMATION |
| | REQUIRED. LATERAL FORCE-RESISTING SYSTEM |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2014 FBC-B 1604.4 ANALYSIS. |
| | |
| | |
| | 10) SHEET A811 DETAIL A10 DETAILS TO X-RAY ROOMS AND |
| | CONTROL ROOM AS WELL AS IN THE 4 TRAUMA UNITS. |
| | . FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL |
| | HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS |
| | NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A |
| | RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN |
| | PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE. |
| | PLEASE SHOW COMPLIANCE WITH: |
| | 10A) FBC-B 465.5.1.1 STRUCTURAL SHIELDING IN WALLS AND |
| | OTHER VERTICAL BARRIERS REQUIRED FOR PERSONNEL |
| | PROTECTION SHALL EXTEND WITHOUT BREACH FROM THE FLOOR |
| | TO A HEIGHT OF AT LEAST 7 FEET (2.1 M). |
| | |
| | 10B) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND |
| | WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT |
| | SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER |
| | IN WHICH THEY ARE INSTALLED. |
| | |
| | 10C) FBC-B 465.5.1.3 PRIOR TO CONSTRUCTION, THE FLOOR |
| | PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW |
| | INSTALLATIONS, OR MODIFICATIONS OF EXISTING |
| | INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND |
| | ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE |
| | SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND |
| | APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER |
| | REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE |
| | FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| | INTO CONSIDERATION. |
| | |
| | 10D) 465.5.1.3.1 THE PLANS SHALL SHOW, AS A MINIMUM, |
| | THE FOLLOWING. |
| | |
| | 465.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM'S |
| | RADIATION PORT; THE PORT'S TRAVEL AND TRAVERSE LIMITS; |
| | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY |
| | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR'S |
| | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. |
| | |
| | 465.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS |
| | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, |
| | FLOOR AND CEILING OF THE ROOM CONCERNED. |
| | |
| | 465.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. |
| | |
| | 465.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT |
| | AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM |
| | CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE |
| | TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS |
| | MAY BE PRESENT. |
| | |
| | 465.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT |
| | AND THE MAXIMUM TECHNIQUE FACTORS. |
| | |
| | 465.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS |
| | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. |
| | |
| | 10E) 465.6 DOORS, INTERLOCKS, AND WARNING SYSTEMS. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |