| Plan Review Notes For Permit 17060047 |
| Permit Number |
17060047 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-05 14:03:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE FA SHALL BE TESTED PER NFPA 72. | | | | | | 14.4.1.2* REACCEPTANCE TESTING. | | | 14.4.1.2.1 REACCEPTANCE TESTING SHALL BE PERFORMED AS | | | REQUIRED IN 14.4.1.2.1.1 THROUGH 14.4.1.2.1.4. | | | 14.4.1.2.1.1 WHEN AN INITIATING DEVICE, NOTIFICATION | | | APPLIANCE, OR CONTROL RELAY IS ADDED, IT SHALL BE | | | FUNCTIONALLY TESTED. | | | 14.4.1.2.1.2 WHEN AN INITIATING DEVICE, NOTIFICATION | | | APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE, | | | APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE | | | OPERATED. | | | 14.4.1.2.1.3 WHEN MODIFICATIONS OR REPAIRS TO CONTROL | | | EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT | | | SHALL BE TESTED IN ACCORDANCE WITH TABLE 14.4.2.2, | | | ITEMS 1(A) AND 1(D). | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|