| 2017-11-13 09:02:49 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060032 |
| | 11/13/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE 24X24 TRANSFER GRILL IS ALLOWING RECIRCULATION |
| | OF AIR FROM THE SALON INTO THE OFFICE AREA WHICH IS |
| | PROHIBITED PER TABLE 403.3 FOOTNOTE B. |
| | |
| | 2) THE PLAN DOES NOT SHOW THE REQUIRED SOURCE CAPTURE |
| | SYSTEMS REQUIRED AT EACH MANI AND PEDI STATION, AND HOW |
| | THE FUMES, VAPORS ETC. ARE BEING EXHAUSTED OUT OF THE |
| | BUILDING. PLEASE SEE SECTION 501.3 WHICH REQUIRES THE |
| | HEALTHY AIR SOURCE CAPTURE SYSTEMS TO BE DUCTED TO THE |
| | OUTDOORS. PLEASE PROVIDE A MEDCHANICAL FLOOR PLAN |
| | DRAWING THAT SHOWS THE STATIONS, THE SYSTEMS, THE |
| | |
| | DUCT RUNS, AND EXHAUST OUTLET LOCATIONS. INDICATE THE |
| | TYPES AND SIZES OF EXHAUST DUCTS TO BE INSTALLED, AND |
| | PROVIDE SUPPORT AND CONNECTION DETAILS. |
| | |
| | 3) THE SUBMITTED PRODUCT INFORMATION SHEETS FOR THE |
| | HEALTHY AIR SYSTEMS DO NOT PROVIDE ANY LISTING OR |
| | LABELING INFORMATION, OR INDICATE THAT THE PRODUCT HAS |
| | BEEN TESTED AND APPROVED BY ANY AGENCIES SUCH AS ETL OR |
| | UL. PLEASE SUBMIT PRODUCT DATA SHEETS WITH SHOP DRAWING |
| | APPROVAL SIGNATURES BY THE ENGINEER OF RECORD. |
| | |
| | 4) PROVIDE EXHAUST VENTILATION CALCULATIONS, AND AIR |
| | BALANCE CALCULATIONS. |
| | |
| | 5) PROVIDE A SEQUENCE OF OPERATION FOR EF-1- SEE |
| | SECTION 501.4 |
| | |
| | 6) IT APPEARS THAT THE NEW CONDENSER IS BEING LOCATED |
| | WITHIN 10' OF THE ROOF EDGE WHICH WOULD REQUIRE A GUARD |
| | OR PARAPET AT A MINIMUM HEIGHT OF 42"- PLEASE COMPLY. |
| | PLEASE NOTE THAT PERMANENT LADDERS ARE REQUIRED FOR |
| | ROOF TOP MECHANICAL EQUIPMENT LOCATED OVWER 16' FROM |
| | GRADE. |
| | |
| | 7) THE ARCHITECTURAL PLANS ARE INDICATING THE AHU-1 |
| | CLOSET DOOR IS WOOD, HOWEVER AC CLOSET DOORS SHALL BE |
| | NON-COMBUSTIBLE IN COMPLIANCE WITH SECTION C403.2.7.2 |
| | FBC-14 ENERGY CONSERVATION AND SECTION 602 FBC-14 |
| | MECHANICAL. PLEASE NOTE THAT THE NO CLOSET WALLS OR |
| | DOOR ARE SHOWN FOR AHU-2 ALTHOUGH THERE IS A NOTE ON |
| | THE PLAN INDICATING A LOUVERED DOOR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |