| 2017-11-15 14:19:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS A 100 AMP PANEL (PANEL A) BEING |
| | FED FROM PANEL B, HOWEVER, THE LOAD FOR PANEL A IS NOT |
| | INCLUDED WITH LOAD CALCULATION. PROVIDE ACCURATE LOAD |
| | CALCULATION WITH ALL LOADS ACCOUNTED FOR TO DETERMINE |
| | IF SERVICE SIZE IS ADEQUATE. BE ADVISED THAT ONLY ONE |
| | SERVICE IS PERMITTED PER LOCATION. NEC 220, 230.2 |
| | 2. PROVIDE PANEL SCHEDULES FOR ALL PANELS INDICATING |
| | ANY NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE |
| | FOR THESE CIRCUITS, AND GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 215.5, 408.4 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 4. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT PER CODE. NEC 210.63 |
| | 5. ELECTRICAL PLAN PROVIDED IS INCOMPLETE. SHOW ALL |
| | EXISTING ELECTRICAL AND ANY NEW INSTALLATIONS RELATING |
| | TO CHANGE OF USE AS A HAIR SALON. FBC 107.2.1, 107.3.5 |
| | 6. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC |
| | 210.62 |
| | 7. PROVIDE DEDICATED SIGN CIRCUIT WITH AUTOMATIC |
| | CONTROL PER CODE. NEC 600.5; FBC CE 405.2.4 |
| | |
| | A COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME AS THERE |
| | IS INFORMATION MISSING FROM THE PLANS SUBMITTED. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |