| 2017-06-08 13:11:44 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17060032 |
| | 6/8/17 |
| | |
| | RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR THE |
| | PROPOSED BEAUTY/NAIL SALON. PLEASE PROVIDE PLANS, |
| | DETAILS, AND SPECIFICATIONS FOR ALL HVAC ALTERATIONS |
| | AND INSTALLATIONS REQUIRED TO ACCOMODATE THE NEW |
| | OCCUPANCY AS OUTLINED IN SECTION 403 AND TABLE 403.3 |
| | FBC-14 MECHANICAL. PLEASE NOTE THAT MECHANICAL EXHAUST |
| | SYSTEMS ARE REQUIRED AND RECIRCULATION OF AIR |
| | |
| | FROM THE SALON OR NAIL STATIONS IS PROHIBITED- SEE |
| | SECTION 403.2.1 ITEM 3. SEE REQUIREMENTS LISTED BELOW. |
| | |
| | A) PROVIDE EXHAUST VENTILATION SYSTEMS FOR THE MANICURE |
| | TABLES AND THE PEDICURE CHAIRS AT A RATE NOT LESS THAN |
| | 50 CFMS PER NAIL STATION. EACH STATION SHALL BE |
| | PROVIDED WITH A SOURCE CAPTURE SYSTEM- SEE FOOTNOTE H |
| | UNDER TABLE 403.3. RECIRCULATION OF THE EXHAUST AIR IS |
| | PROHIBITED- FOOTNOTE B |
| | |
| | B) PROVIDE EXHAUST VENTILATION SYSTEM FOR THE BEAUTY |
| | SALON AT AN EXHAUST RATE OF 0.6 CFMS PER SF- TABLE |
| | 403.3. |
| | |
| | C) PROVIDE A MEANS OF MAKEUP AIR FOR THE EXHAUST |
| | SYSTEMS- 501.4. |
| | |
| | D) CALCULATIONS REQUIRED: EXHAUST, OUTDOOR AIR FOR ALL |
| | OCCUPIED ROOMS AND SPACES, AND AIR BALANCE. |
| | |
| | E) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC |
| | SYSTEM THAT LISTS THE MAKE AND MODEL AND COOLING AND |
| | HEATING CAPACITIES OF THE SYSTEM. |
| | |
| | 2) PLEASE SEE BUILDING REVIEW COMMENTS #1E AND #2 FOR |
| | EXTERIOR MECHANICAL EQUIPMENT AND APPLIANCE |
| | INSTALLATION REQUIREMENTS. |
| | |
| | 3) PLEASE NOTE FURTHER COMMENTS MAY FOLLOW THIS REVIEW |
| | AFTER CORRECTED AND REVISED PLANS ARE RESUBMITTED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |