| 2017-06-05 08:57:45 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17060024 |
| | ADD: 930 OMAR RD. |
| | CONT: STATEWIDE WINDOWS & DOORS |
| | TEL: 561-202-1412 |
| | E-MAIL: SCOTT.STATEWIDEWINDOWS @GMAIL.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 05/2017 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED FLOOR PLAN DOES NOT HAVE WHO THE |
| | AUTHOR OF THE FLOOR PLAN IS. THE QUALIFIER FOR THE |
| | COMPANY SHOULD PRINT THEIR NAME, SIGN THEIR NAME AND |
| | CONTRACTOR LICENSE NUMBER ON THE PLANS TAKING OWNERSHIP |
| | OF THE PLANS. 105.3.1.2. / 107.3.4.3 CERTIFICATIONS BY |
| | CONTRACTORS. |
| | |
| | 2A) THE SUBMITTED FLOOR PLAN INDICATES (2) BEDROOMS |
| | WITH WINDOWS (5-8) BEING LOCATED IN THE (2) BEDROOMS. |
| | STATEWIDE ORDER FORM DATED 3/1/17 HAS ALL FOUR OF THESE |
| | WINDOWS LABELED SH (SINGLE HUNG) WINDOWS. PLEASE NOTE |
| | WINDOW # 5 IS 36(W)X(50(H) IN DIMENSIONS OR APPROX. |
| | (CLEAR OPENING)32 INCHES WIDE X 19 INCHES IN HEIGHT AND |
| | A NET CLEAR OPENING OF 4.25 SQ. FT. DOES NOT MEET THE |
| | EGRESS REQUIREMENTS. |
| | |
| | WINDOWS 6-8 STILL THE BEDROOM WINDOWS ALL SHOW 36 IN. |
| | (W)X 38 IN. (H)WITH AN APPROX.. CLEAR OPENING OF 3.18 |
| | SQ. FT. DOES NOT MEET THE EGRESS REQUIREMENTS. |
| | |
| | |
| | 2014 FBC-R SECTION R310 EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS R310.1. EMERGENCY ESCAPE AND RESCUE REQUIRED. |
| | BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| | SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND |
| | RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE |
| | SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS |
| | SHALL BE REQUIRED IN EACH SLEEPING ROOM. WHERE |
| | EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY |
| | SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES |
| | (1118 MM) MEASURED FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE CLEAR OPENING. |
| | |
| | 2014 FBC-R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET |
| | CLEAR OPENING OF 5.7 SQUARE FEET (0.530 M2). |
| | EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM |
| | NET CLEAR OPENING OF 5 SQUARE FEET . |
| | |
| | R310.1.2 MINIMUM OPENING HEIGHT. THE MINIMUM NET CLEAR |
| | OPENING HEIGHT SHALL BE 24 INCHES . |
| | |
| | R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR |
| | OPENING WIDTH SHALL BE 20 INCHES. |
| | |
| | R310.1.4 OPERATIONAL CONSTRAINTS. |
| | EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE |
| | OPERATIONAL FROM THE INSIDE OF THE ROOM WITHOUT THE USE |
| | OF KEYS, TOOLS OR SPECIAL KNOWLEDGE. |
| | 2014 FBC-EXISTING BUILDING CODE SECTION 704 MEANS OF |
| | EGRESS (WINDOWS) |
| | 704.1. MEANS OF EGRESS FOR BUILDINGS UNDERGOING |
| | ALTERATION SHALL COMPLY WITH THE REQUIREMENTS OF |
| | SECTION 701.1 AND THE SCOPING PROVISIONS OF CHAPTER 1 |
| | WHERE APPLICABLE. |
| | EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL |
| | DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5-PERCENT |
| | REDUCTION IN THE CLEAR OPENING DIMENSIONS OF |
| | REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED. |
| | |
| | 2B) DISCREPANCIES WITH THE STATEWIDE ORDER FORM DATED |
| | 3/1/17 AND THE CUSTOM WINDOW SYSTEMS. THE STATEWIDE |
| | FORM LIST ALL OF THE WINDOWS AS SINGLE HUNG WHEREAS |
| | CUSTOM WINDOW FORM HAS 2 LINE ITEMS, NUMBER 4 WITH |
| | QUANTITY (1) HORIZONTAL SLIDER TIP 74 1/8 IN. X 38 3/8 |
| | IN. AND LINE ITEM NUMBER 5 WITH QUANTITY (2) HORIZONTAL |
| | SLIDER TIP 74 1/8 IN. X 38 3/8 IN. THE SAME AS LINE |
| | ITEM NUMBER 4, WHAT IS THE DIFFERENCE? 107. 2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2C)IN THE CUSTOM WINDOW FORM ITEMS NUMBERED 4 & 5 |
| | HORIZONTAL SLIDER TIP 74 1/8 IN. X 38 3/8 IN THIS IS AN |
| | OVERALL DIMENSION FOR A SINGLE SLIDER WINDOW IT WOULD |
| | APPEAR THESE WINDOWS ARE FOR THE WINDOWS 11-14 NOT |
| | PROVIDED ON THE STATEWIDE FORM DATED 3/1/17. 107. 2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |