Plan Review Notes
Plan Review Notes For Permit 17060007
Permit Number 17060007
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-15 15:54:431ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASHING MACHINE AND LAUNDRY TRAY SHALL NOT BE
 USED TO WET VENT THE TUB AND SHOWER. TUB AND SHOWER
 SHALL BE WET VENTED BY THE LAVATORY AS PART OF THE
 BATHROOM GROUP. PER FBC PL 912.1
  
 2. THE WASHING MACHINE BRANCH DRAIN SHALL CONNECT TO
 VERTICAL STACK TO BE VENTED PROPERLY. PER FBC PL
 901.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  