Plan Review Notes
Plan Review Notes For Permit 17060007
Permit Number 17060007
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-19 09:10:38CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. RISER DIAGRAM DOES NOT SHOW SUFFICIENT DETAIL. WHICH
 PANEL WILL BE FED FROM THE TRANSFER SWITCH? THE DRAWING
 CURRENTLY SHOWS THE MDP FEEDING BOTH PANELS AND TYING
 INTO THE TRANSFER SWITCH, BUT I SEE NO LOAD ON THE
 TRANSFER SWITCH. PROVIDE CORRECTION/CLARIFICATION. IF
 THE TRANSFER SWITCH FEEDS BOTH PANELS, PROVIDE PROPER
 SIZE OF TRANSFER SWITCH TO HANDLE LOAD. FBC 107.2.1 ,
 107.3.5, NEC 215.5
 2. PROVIDE PANEL SCHEDULE/SIZING FOR PANEL MDP. NEC
 408.4, 408.30 FBC RE3706.1
 3. SHOW LOCATION ON PLAN FOR PANEL MDP AND TRANSFER
 SWITCH. FBC 107.2.1
 4. PROVIDE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. THE LOAD CALCULATION ON PLAN IS NOT CLEARLY
 EXPLAINED. NEC 220, FBC 107.2.1
 5. PANEL SCHEDULE FOR PANEL A SHOWS CIRCUIT 9 AND 10 AS
 A 60 AMP CIRCUIT ON #12 WIRE. PROVIDE CORRECTION. NEC
 240.4(D) FBC RE3705.1
 6. PANEL SCHEDULE FOR PANEL A SHOWS CIRCUITS
 17,19,21,23,25,27,8,20,22,24, AND 26 AS A 20 AMP
 CIRCUIT ON #14 WIRE. PROVIDE CORRECTION. NEC 240.4(D)
 FBC RE3705.1
 7. A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS. PROVIDE NOTE TO SHOW COMPLIANCE. FBC EC
 R404.1
 8. PROVIDE SMOKE/CARBON MONOXIDE DETECTORS IN ALL
 LOCATION REQUIRED BY CODE. MANY ARE MISSING IN THE
 AREAS ADJACENT TO BEDROOMS. PROVIDE NOTE THAT ALL
 ALARMS WILL BE INTERCONNECTED. FBC R314, R315
 9. LIGHTING SHOWN IN CLOSETS FOR BEDROOM 2 AND 3 IS NOT
 TO CODE. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOSETS. PROVIDE CORRECTION. NEC
 410.16(B), FBC RE4003.12
 10. PROVIDE GFCI OUTLET ON REAR OF HOUSE AS REQUIRED BY
 CODE. NEC 210.52(E)(1) FBC RE3901.7
 11. PROVIDE SWITCH CONTROLLED LIGHT AT EACH ENTRY/EXIT
 OF HOUSE. "AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS,
 ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC
 POWER. AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON
 THE EXTERIOR SIDE OF EACH OUTDOOR EGRESS DOOR HAVING
 GRADE LEVEL ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR
 ATTACHED GARAGES AND DETACHED GARAGES WITH ELECTRIC
 POWER. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR EGRESS DOOR. WHERE ONE OR MORE
 LIGHTING OUTLETS ARE INSTALLED FOR INTERIOR STAIRWAYS,
 THERE SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL AND
 LANDING LEVEL THAT INCLUDES AN ENTRYWAY TO CONTROL THE
 LIGHTING OUTLETS WHERE THE STAIRWAY BETWEEN FLOOR
 LEVELS HAS SIX OR MORE RISERS". NEC 210.70(A)(2)(B) FBC
 RE3903.3
 12. PROVIDE INDICATION OF AFCI PROTECTION PER CODE.
 "ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION". NEC 210.12, FBC RE3902.12
 13. PROVIDE INDICATION OF TAMPER RESISTANT RECEPTACLES.
 A NOTE SHALL SUFFICE FOR THIS. NEC 406.12 FBC RE4002.14
 14. SHOW OUTLETS FOR CENTRAL VAC SYSTEM. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved