| 2017-06-28 11:41:35 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. ROOFING PERMIT REQUIRED. ROOFING REVIEW APPROVED. |
| | |
| | 2. PALM BEACH COUNTY IMPACT FEES WILL BE REQUIRED. |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. |
| | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE |
| | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN |
| | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP |
| | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE |
| | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY |
| | IMPACT FEES AT (561) 233-5025. |
| | |
| | 3. INSULATION - PROVIDE ICC-ES REPORT AND MANUFACTURERS |
| | INSTALLATION INSTRUCTIONS FOR THE PROPOSED R20 ICYNENE |
| | INSULATION. DESIGNER TO SELECT ICYNENE PRODUCT TO BE |
| | USED. |
| | R402.1.1 INSULATION AND FENESTRATION CRITERIA. |
| | THE BUILDING THERMAL ENVELOPE SHALL MEET THE |
| | REQUIREMENTS OF TABLE R402.1.1 BASED ON THE CLIMATE |
| | ZONE SPECIFIED IN CHAPTER 3. |
| | |
| | 3. PROVIDE SITE DRAINAGE PLAN. |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. |
| | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES WITHIN THE FIRST 10 FEET. |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 |
| | FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE |
| | DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING |
| | FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY |
| | FROM THE BUILDING. |
| | |
| | DEFINED FIELDS - INTERNAL USE ONLY |
| | |
| | USC-404 ? NEW: SFR, DETACHED |
| | |
| | CONSTRUCTION TYPE ? 5TH ED TYPE VB |
| | UNITS: - 1 |
| | FLOORS: - 1 |
| | BEDROOMS: - 3 |
| | ROOMS: - 16 |
| | SQ FT LIVABLE: - 3176 |
| | SQ FT FOOTPRINT: - 4497 |
| | SQ FT ROOF: - 3949 |
| | |
| | SETBACKS FRONT ? 56? 1? (USE THIS TO ENTER VERTICAL |
| | DATUM IF KNOWN): NGVD29 |
| | SETBACKS BACK ? 68? 5? (USE THIS TO ENTER FIRST FLOOR |
| | IF KNOWN): XX.XX |
| | SETBACKS LEFT ? 25? 8? (USE THIS TO ENTER SECOND FLOOR |
| | IF KNOWN: XX.XX |
| | OCC LOAD: - R3 |
| | PROP USE: - SFR |
| | SPRINKLER SYS? - NO |
| | SPRK REQ'D? - NO |
| | BATHRMS: - 3 |
| | |
| | BLDG CODE: - FL 2014 |
| | OCC CLASS: - 5TH ED R3 |
| | |
| | |
| | |
| | |
| | |