| Notes |
| Date |
Text |
| 2018-09-19 10:53:09 | | | | PROVISOS: | | | | | | 1. RESTRICTIVE COVENANT TO BE PLACED ON ADJACENT | | | PROPERTY NOT ALLOWING FUTURE STRUCTURES WITHIN REQUIRED | | | SEPARATION DISTANCE FROM PARKING STRUCTURE LOCATED ON | | | PROPERTY LINE. | | | | | | 2. PROVIDE REVISION TO ADD TWO FANS IN THE LOWER LEVEL | | | OF PARKING GARAGE TO OPERATE ON CO SENSOR. | | | | | | 3. PROVIDE REVISION OF STRUCTURAL DRAWINGS TO INCLUDE | | | ANY STRUCTURAL CHANGES DUE TO INCREASED OPENINGS AND | | | 2ND LEVEL CANOPY COVERING IF AFFECTED BY FINAL ROOF | | | COVERING LAYOUT. | | | | | | 4. PROVIDE RESIDENT INSPECTOR FORM WITH ALL THREE | | | ENGINEERS ON ONE FORM. PROVIDE RESUMES FOR ANDREW | | | SULLIVAN AND CHAD CASSETT. WE HAVE RESUME FOR SERGIO | | | GONZALEZ. | | | | | | |
|