Plan Review Notes
Plan Review Notes For Permit 17060001
Permit Number 17060001
Review Stop B
Sequence Number 3
Notes
Date Text
2018-09-04 12:23:29****CORRECTIONS****
 W.P.B. PERMIT: 17060001
 3RD REVIEW: SEPTEMBER 4, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC A = ACCESSIBILITY
  
 1. OK.
  
 2. OK.
  
 3. SP1.0, STRUCTURE IS SHOWN ON THE PROPERTY LINE WITH
 OPENINGS ON THE PROPERTY LINE. SEE FBC B TABLE 705.8
 AND REVISE TO SHOW COMPLIANCE. ALSO NOTE THAT THESE
 OPENINGS ARE USED TO SHOW COMPLIANCE WITH OPEN PARKING
 GARAGE OPENINGS. HOW WILL YOU GUARANTEE THAT THIS AREA
 WILL NOT BE OBSTRUCTED, BUT STRUCTURES OR LANDSCAPING
 WHICH COULD RESTRICT THE OPEN AIR FLOW?
  
 3-3. [FBC B TABLE 705.8]SEE OPENINGS BASED ON FIRE
 SEPARATION FROM TABLE 705.8. PLEASE SEE NEW COMMENT #15
 TO ADDRESS OPENINGS AS THEY RELATE TO OPEN GARAGE VS.
 CLOSED.
  
 4. OK.
  
 5. SHEET A1.2.01, TRAVEL DISTANCE FROM FIRST FLOOR
 WHICH IS PARTIALLY BELOW GRADE AS ENDING AT THE STAIR.
 TRAVEL DISTANCE IS TO BE MEASURED TO AN EXIT. SEE
 DEFINITION OF EXIT, CHAPTER 2. THE STAIRS ARE NOT
 NUMBERED OR OTHERWISE IDENTIFIED, SO I'LL CALL THEM
 "NORTH STAIR" AND "SOUTH STAIR". REVISE PLAN TO CLARIFY
 TRAVEL DISTANCE.
  
 5-3. TRAVEL PATH WAS ADJUSTED, BUT IT NOW SHOWS A
 TRAVEL DISTANCE > THAN 250?. THIS MAY BE A TYPE O AS
 THERE IS EXIT STAIR WITHIN 250?. P
  
 6. OK.
  
 7. OK.
  
 8. A1.2.01, OCCUPANT LOAD IS SHOWN AS 1 ON THE LIFE
 SAFETY PLAN, REVISE AS THE AREA OF FIRST FLOOR IS
 LARGER THAN 200SF. IT IS NOTED AS "NOT ENCLOSED", BUT
 APPEARS TO HAVE TWO SIDES ENTIRELY OBSTRUCTED AND ONE
 SIDE ALMOST ENTIRELY OBSTRUCTED (BY WALLS). DIMENSIONS
 AND SQUARE FOOT AREA WERE NOT PROVIDED ON THE LS
 SHEETS.
  
 37,999 SF IS SHOWN AS AREA FOR FIRST FLOOR, WHICH
 RESULTS IN 190 OCCUPANTS. REVISE LIFE SAFETY PLAN
 ACCORDINGLY.
  
 8-3. [FBC B 1004.1.2]SHEETS A-1.2.01 AND A-1.2.02 USE
 OCCUPANCY FACTOR OF 300 SQ. FT.
 SEE TABLE 1004.1.2 WHERE PARKING GARAGE USE 200 SQ. FT.
 PER OCCUPANT.
  
 9. OK.
  
 10. OK. (THIS WILL BE ADDRESSED IN COMMENT 5-3 ABV.)
  
 11. FBC A 206.2.3, VERTICAL ACCESSIBLITY REQUIRED. SEE
 ALSO FBC A 206.3 AND ADVISORY; CIRCULATION PATHS ARE TO
 COINCIDE WITH GENERAL CIRCULATION. AN INTERIOR
 ACCESSIBLE PATH FROM FIRST FLOOR TO THE 2ND FLOOR WHICH
 COINCIDES WITH THE GENERAL CIRCULATION IS REQUIRED.
  
 11-3. PENDING APPROVAL FROM BUILDING OFFICIAL.
  
 12. FBC A 208.3.1 AND ADVISORY, ACCESSIBLE PARKING IS
 REQUIRED ON THE FIRST FLOOR, AS IS VAN ACCESSIBLE
 PARKING. YOU CANNOT PROVIDE INTERIOR COVERED PARKING
 WITHOUT ANY ACCESSIBLE INTERIOR COVERED PARKING.
 PARKING CAN BE DISTRIBUTED.
  
 12-3. PENDING APPROVAL FROM BUILDING OFFICIAL.
  
 13. A3.1.01 APPEARS TO SHOW 7'11" CLEAR HEIGHT FIRST
 FLOOR PARKING; THIS DOES NOT MEET THE HEIGHT
 REQUIREMENT FOR VAN ACCESSIBLE PARKING, FBC A 502.5.
 REVISE TO SHOW COMPLIANCE.
  
 13-3. PENDING APPROVAL FROM BUILDING OFFICIAL.
  
 14. A1.2.02, ACCESSIBLE PARKING SPACES ON THE NORTH
 SIDE NOTE THAT THERE IS AN ADJACENT SIDEWALK AND LAWN.
 WHAT ABOUT THE OTHER SIDE? IS THE LAWN TO BE USED FOR
 ACCESSIBLE ROUTE? FBC A 502.
  
 14-3 ACCESSIBLE PARKING HAS BEEN RE-ARRANGED FROM
 PREVIOUS PERIMETER LAYOUT. THIS NEW ARRANGEMENT
 DEVIATES FROM THE APPROVED SITE PLAN AND NOW BRINGS
 INTO QUESTION HOW IT MEETS ACCESSIBILITY CODES 502.3
 AND FLORIDA STATUTE 553.401(5)(A).
 PLEASE CLARIFY IF SITE PLAN IS BEING ADJUSTED AND HOW
 ACCESS AISLE WORKS WITHOUT LEADING PERSONS TO WALK
 BEHIND PARKED VEHICLES.
 ALSO, SHEET A-1.0.02, MEP SHEETS, LANDSCAPING SHEETS
 AND SITE PLAN SHOW ORIGINAL PARKING LAYOUT. PLEASE
 CO-ORDINATE ALL SHEETS TO MATCH APPROVED PARKING
 LAYOUT.
  
 NEW COMMENT:
 15. [FBC B SECTION 406]ELEVATION DRAWINGS STATE
 COMPLIANCE WITH THE OPENING REQUIREMENTS FOR OPEN
 GARAGE. HOWEVER, I DON?T SEE THE CALCULATIONS AS TO HOW
 THIS WAS DERIVED. PLEASE PROVIDE THE CALCULATIONS TO
 SHOW HOW 20% OF THE TOTAL WALL AREA OF LOWER TIER IS
 BEING PROVIDED OVER 40% OF THE PERIMETER.
 IF THIS TIER IS CODE DEFINED AS ENCLOSED THAN
 PROVISIONS OF 406.6 FOR ENCLOSED GARAGE WILL APPLY.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  