2018-05-27 18:33:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. GENERAL COMMENT - THE DIGITAL FILE NAMES DO NOT
 INCLUDE ANY DESCRIPTIONS. IT IS CUSTOMARY FOR PAGES TO
 INCLUDE PAGE NAME. FAILURE TO PROVIDE THIS INFORMATION
 SLOWS DOWN REVIEW. NO NEED TO ADDRESS FOR THIS PERMIT,
 BUT FUTURE SUBMITTALS SHOULD HAVE A NAMING CONVENTION
 THAT FACILITATES PLAN REVIEW. PAGES ARE NOT IN ORDER -
 SITE PLAN IS BURIED IN THE MIDDLE OF THE PLAN, S2.02B
 IS WRONG LOCATION DUE TO WRONG NAME. INCORRECT NAMING
 MAKES PLAN REVIEW DIFFICULT. YOU DO NOT NEED TO RENAME
 EVERY PAGE BUT YOU DO NEED TO FIX THE PAGES WHICH ARE
 NOT IN THE CORRECT LOCATIONS; RENAME SO THEY CORRELATE
 WITH THE INDEX.
  
 2. GENERAL COMMENT - SEE DEFINITION OF "BUILDING" FBC B
 CHAPTER 2, FBC B 1001.1. THIS STRUCTURE - A PARKING
 GARAGE WITH WALLS THAT ALSO ACT AS RETAINING WALLS ON
 THREE SIDES, ONE OPEN SIDE, ROOF WHICH SERVES AS
 PARKING AT GRADE, DUE TO SITE ELEVATIONS. FIRST FLOOR
 IS PARTIALLY UNDER GROUND. THIS DESCRIPTION IS PROVIDED
 FOR THE BENEFIT OF THOSE WHO ARE UNFAMILIAR WITH THE
 STRUCTURE WHICH IS UNUSUAL FOR FLORIDA.
  
 3. SP1.0, STRUCTURE IS SHOWN ON THE PROPERTY LINE WITH
 OPENINGS ON THE PROPERTY LINE. SEE FBC B TABLE 705.8
 AND REVISE TO SHOW COMPLIANCE. ALSO NOTE THAT THESE
 OPENINGS ARE USED TO SHOW COMPLIANCE WITH OPEN PARKING
 GARAGE OPENINGS. HOW WILL YOU GUARANTEE THAT THIS AREA
 WILL NOT BE OBSTRUCTED, BUT STRUCTURES OR LANDSCAPING
 WHICH COULD RESTRICT THE OPEN AIR FLOW?
  
 4. SEE SIGNATURE REVIEW REGARDING TITLE BLOCK FOR MEP
 ENGINEER PAGES; SEE ALSO ADDRESS REVIEW.
  
 5. SHEET A1.2.01, TRAVEL DISTANCE FROM FIRST FLOOR
 WHICH IS PARTIALLY BELOW GRADE AS ENDING AT THE STAIR.
 TRAVEL DISTANCE IS TO BE MEASURED TO AN EXIT. SEE
 DEFINITION OF EXIT, CHAPTER 2. THE STAIRS ARE NOT
 NUMBERED OR OTHERWISE IDENTIFIED, SO I'LL CALL THEM
 "NORTH STAIR" AND "SOUTH STAIR". REVISE PLAN TO CLARIFY
 TRAVEL DISTANCE.
  
 6. NORTH STAIR AND SOUTH STAIR HAVE A SINGLE LINE
 AROUND THE STAIR AREAS BUT IT IS NOT CLEAR WHAT THESE
 LINES DEPICT, FBC 107. PLEASE CLARIFY.
  
 7. EXIT #1 IS SHOWN WITHOUT ANY OCCUPANTS TRAVELLING TO
 THIS EXIT. EXPLAIN THE RATIONALE OF HAVING ALL
 OCCUPANTS TRAVEL UP A FLIGHT OF STAIRS TO EXIT THE
 BUILDING WHEN THEY ENTERED AT GRADE.
  
 8. A1.2.01, OCCUPANT LOAD IS SHOWN AS 1 ON THE LIFE
 SAFETY PLAN, REVISE AS THE AREA OF FIRST FLOOR IS
 LARGER THAN 200SF. IT IS NOTED AS "NOT ENCLOSED", BUT
 APPEARS TO HAVE TWO SIDES ENTIRELY OBSTRUCTED AND ONE
 SIDE ALMOST ENTIRELY OBSTRUCTED (BY WALLS). DIMENSIONS
 AND SQUARE FOOT AREA WERE NOT PROVIDED ON THE LS
 SHEETS.
  
 37,999 SF IS SHOWN AS AREA FOR FIRST FLOOR, WHICH
 RESULTS IN 190 OCCUPANTS. REVISE LIFE SAFETY PLAN
 ACCORDINGLY.
  
 9. SHEET A-0.0.02, PROJECT DATA, DOES NOT GIVE SQUARE
 FOOT AREA OF THIS STRUCTURE. IT IS NOT CLEAR HOW
 COMPLIANCE WITH FBC B CHAPTER 5, BUILDING HEIGHT AND
 AREA, IS DEMONSTRATED. REVISE TO INCLUDE AREAS, REVISE
 TO SHOW COMPLIANCE INCLUDING APPLICABLE EXCEPTIONS AND
 AREA INCREASES.
  
 10. SEE FBC B 1007, FBC A 207.1, IBC 2000/IBC 2003
 (PLEASE ADVISE WHICH METHOD IS SELECTED). TWO EXITS ARE
 REQUIRED FROM THE FIRST FLOOR. IT APPEARS THAT ALTHOUGH
 A LARGE PORTION OF THE BUILDING IS OPEN, ACCESS TO THE
 OUTSIDE AND PUBLIC WAY ARE OBSTRUCTED BY WALLS AND
 PARKING SPACES. THE SAME NUMBER OF ACCESSIBLE EXITS ARE
 REQUIRED AS EXITS REQUIRED BY FBC CHAPTER 10.
 EXITS/MEANS OF EGRESS AND ACCESSIBLE MEANS OF EGRESS
 NOT CLEAR. REVISE TO SHOW COMPLIANCE.
  
 11. FBC A 206.2.3, VERTICAL ACCESSIBLITY REQUIRED. SEE
 ALSO FBC A 206.3 AND ADVISORY; CIRCULATION PATHS ARE TO
 COINCIDE WITH GENERAL CIRCULATION. AN INTERIOR
 ACCESSIBLE PATH FROM FIRST FLOOR TO THE 2ND FLOOR WHICH
 COINCIDES WITH THE GENERAL CIRCULATION IS REQUIRED.
  
 12. FBC A 208.3.1 AND ADVISORY, ACCESSIBLE PARKING IS
 REQUIRED ON THE FIRST FLOOR, AS IS VAN ACCESSIBLE
 PARKING. YOU CANNOT PROVIDE INTERIOR COVERED PARKING
 WITHOUT ANY ACCESSIBLE INTERIOR COVERED PARKING.
 PARKING CAN BE DISTRIBUTED.
  
 13. A3.1.01 APPEARS TO SHOW 7'11" CLEAR HEIGHT FIRST
 FLOOR PARKING; THIS DOES NOT MEET THE HEIGHT
 REQUIREMENT FOR VAN ACCESSIBLE PARKING, FBC A 502.5.
 REVISE TO SHOW COMPLIANCE.
  
 14. A1.2.02, ACCESSIBLE PARKING SPACES ON THE NORTH
 SIDE NOTE THAT THERE IS AN ADJACENT SIDEWALK AND LAWN.
 WHAT ABOUT THE OTHER SIDE? IS THE LAWN TO BE USED FOR
 ACCESSIBLE ROUTE? FBC A 502.
  