| 2018-02-28 11:32:45 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | PERMIT #17060001 | | | 2/28/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE BUILDING SHALL BE IN COMPLIANCE WITH THE 2014 | | | FLORIDA ENERGY CONSERVATION CODE, AND AN ENERGY | | | COMPLIANCE REPORT MUST BE SUBMITTED UNLESS THE BUILDING | | | IS QUALIFYING AS AN EXEMPT BUILDING PER SECTION | | | C101.4.8. PLEASE PROVIDE A COMPLIANCE REPORT, OR | | | PROVIDE EVIDENCE ON THE PLAN OR IN DOCUMENT FORM THAT | | | THE BUILDING IS EXEMPT. | | | | | | 2) PROVIDE VENTILATION CALCULATIONS FOR THE STORAGE | | | ROOMS- TABLE 403.1 FBC-14 MECHANICAL | | | | | | 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | SYSTEMS IN THE ELECTRICAL ROOMS. | | | | | | 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE AC CONDENSER ON THE ELECTRICAL ROOM WALL- SECTION | | | 301.15 | | | | | | 5) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S | | | FOR THE AIR INTAKE AND EXHAUST OUTLET LOUVERS- RULE | | | 9N-03 FAC. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|