2018-02-28 11:32:451ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #17060001
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BUILDING SHALL BE IN COMPLIANCE WITH THE 2014
 FLORIDA ENERGY CONSERVATION CODE, AND AN ENERGY
 COMPLIANCE REPORT MUST BE SUBMITTED UNLESS THE BUILDING
 IS QUALIFYING AS AN EXEMPT BUILDING PER SECTION
 C101.4.8. PLEASE PROVIDE A COMPLIANCE REPORT, OR
 PROVIDE EVIDENCE ON THE PLAN OR IN DOCUMENT FORM THAT
 THE BUILDING IS EXEMPT.
  
 2) PROVIDE VENTILATION CALCULATIONS FOR THE STORAGE
 ROOMS- TABLE 403.1 FBC-14 MECHANICAL
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 SYSTEMS IN THE ELECTRICAL ROOMS.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE AC CONDENSER ON THE ELECTRICAL ROOM WALL- SECTION
 301.15
  
 5) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S
 FOR THE AIR INTAKE AND EXHAUST OUTLET LOUVERS- RULE
 9N-03 FAC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  