2018-02-08 17:54:37PERMIT # 17060001
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET A-0.0.01: DRAWING INDEX LISTS FIRE PROTECTION
 SHEETS, HOWEVER THESE SHEETS WERE NOT PROVIDED IN THE
 SUBMISSION. PLEASE PROVIDE FIRE PROTECTION SHEETS.
  
 2) SHEET A-0.0.02: BUILDING CONSTRUCTION IS LISTED AS
 TYPE IV. PER NFPA 88A, CHAPTER 5: BUILDING CONSTRUCTION
 SHALL BE OF TYPE I OR TYPE II. PLEASE REVIEW AND
 PROVIDE CORRECTION OR EXPLANATION.
  
 3) SHEET A-0.0.02: NOTES INDICATE THAT THIS STRUCTURE
 WILL BE PROTECTED BY AN APPROVED FIRE SPRINKLER SYSTEM,
 INSTALLED PER NFPA 13. PLEASE CONFIRM AND PROVIDE
 ADDITIONAL DETAILS, AS REQUIRED FOR MASTER PLAN REVIEW.
  
 4) THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS
 NOT ALL DRAWING SHEETS WERE PROVIDED. ADDITIONAL
 COMMENTS MAY BE ISSUED UPON RECEIPT OF MISSING SHEETS
 AND DETAILS.
  
  