Plan Review Notes For Permit 17051281
Permit Number 17051281
Review Stop M
Sequence Number 2
Notes
Date Text
2017-07-05 12:01:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051281
 7/5/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EXCEPTION UNDER SECTION 504.6.4.1 TO ALLOW
 BOOSTER FANS FOR DRYER EXHAUST DUCTS WAS REMOVED FROM
 THE LATEST 2014 FIFTH EDITION OF THE MECHANICAL CODE.
 MAXIMUM LENGTH OF THE DRYER EXHAUST DUCT SHALL BE 35
 FT. WITH REDUCTIONS FOR FITTINGS- SEE TABLE 504.6.4.1.
 EXHAUST DUCT LENGTH MAY ALSO BE DETERMINED BY
 MANUFACTURER'S SPECIFICATIONS - SECTION 504.6.4.2.
 PLEASE SUBMIT THE SPECS.
  
 2) PLEASE PROVIDE THE MAKE AND MODEL OF THE
 RECIRCULATING KITCHWEN EXHAUST HOOD ON THE PLANS, AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 505.
  