| Plan Review Notes For Permit 17051281 |
| Permit Number |
17051281 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-10 09:44:51 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS (2ND REVIEW): | | | | | | 1. PROVIDE CORRECTION FOR FIRE ALARM SYSTEM. SMOKE | | | ALARM SYSTEM IN UNIT SHALL NOT ACTUATE THE BUILDING | | | FIRE ALARM SYSTEM. NFPA 101, 9.6.2.10.4 | | | 2. PROVIDE LOCATION ON PLAN OF SMOKE ALARMS, INDICATING | | | POWER SOURCE AND INTERCONNECTION AS REQUIRED PER FBC | | | 907.2.11 | | | 3. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND | | | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE | | | PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC | | | 410.16 | | | 4. PROVIDE LIGHT FIXTURE SCHEDULE AND SPEC SHEET FOR | | | EACH FIXTURE TO CONFIRM LISTING AND USE. NEC 110.3; FBC | | | 107.2.1 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|