2017-06-13 09:54:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. ID-2.5 ON THE MASTER BATH RISER IT IS SHOWING
 THE NEW SHOWER ABOVE THE FLOOR LEVEL IS THIS CORRECT
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. BRANCH DRAIN FOR WASHING MACHINE SHALL BE 3". PER
 FBC PL 406.2
  
 3. THE WASHING MACHINE DRAIN SHALL BE SEPARATELY
 VENTED. PER FBC PL 901.2.1
  
 4. IS THE WATER HEATER BEING REPLACED IF SO PLACE NOTE
 ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  