2017-06-06 07:57:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051281
 6/6/17
  
 RESULTS: DENIED.
  
 1) THE PLAN SHOWS 1900 CFMS OF SUPPLY AIR BEING
 PROVIDED BY AN EXISTING 2-TON UNIT WHICH FAR EXCEEDS
 THE UNIT'S CAPACITY- PLEASE CORRECT OR CLARIFY. PLEASE
 NOTE THERE IS A 4" DUCT DROP IN THE POWDER ROOM
 INDICATED AT 200 CFMS WHICH EXCEEDS THE CAPACITY OF A
 4" DUCT- SEE THE DUCT SIZE PREVIEW WHICH INDICATES 10
 CFMS FOR THE POWDER ROOM.
  
 2) MISSING FROM THE DUCT SIZING PREVIEW ARE THE LAUNDRY
 ROOM, THE STORAGE ROOM, AND CAROLYN'S BED AND BATHROOM.
  
 3) PROVIDE A COMPLETE DRYER EXHAUST PLAN THAT INCLUDES
 THE TOTAL LENGTH OF THE DRYER RUN FROM OUTLET TO DRYER
 TERMINATION LOCATION, CLARIFY IF THE NEW EXHAUST DUCT
 IS CONNECTING INTO AN EXISTING CHASE AND SHOW THE
 LOCATION AND HOW CONNECTION IS BEING MADE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER-
 SECTION 504.
  
 4) PROVIDE COMPLETE KITCHEN EXHAUST PLANS FOR THE NEW
 COOKING APPLIANCES. SHOW THE TYPES AND SIZES OF EXHAUST
 HOODS, EXHAUST DUCTS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE APPLIANCES AND THE HOODS. SHOW
 THE EXHAUST DUCT RUNS FROM THE EXHAUST OUTLETS TO
 TERMINATION LOCATIONS. IF CONNECTING INTO A CHASE,
 INDICATE SHOW CONNECTION IS BEING MADE. PLEASE NOTE
  
 THAT SEPARATE CHASES ARE REQUIRED FOR KITCHEN EXHAUST,
 DRYER EXHAUST AND BATH EXHAUST- SECTION 501.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719