| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | INDICATE THE SIZE, RATING, AND LOCATION OF THE EXISTING |
| | PANEL BOARD. VERIFY THE REQUIRED WORKING CLEARANCES ARE |
| | MAINTAINED AT THE ELECTRICAL PANEL. NEC 110.26 |
| | |
| | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC |
| | 406.12 |
| | |
| | VERIFY ALL NEW RECEPTACLE CIRCUITS ARE AFCI PROTECTED. |
| | NEC 210.12 |
| | |
| | RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER |
| | REQUIRE GFCI PROTECTION. NEC 210.8 |
| | |
| | VERIFY THE EXISTING AC UNITS HAVE THE REQUIRED |
| | DISCONNECTS. NEC 422.30 |
| | |
| | VERIFY OR PROVIDE A 20 AMP LAUNDRY CIRCUIT WITH GFCI |
| | PROTECTION. NEC 210.11 (C) (2) |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED ON EACH |
| | BALCONY. NEC 210.8, 210.52(E)(3) |
| | |
| | PROVIDE A FIRE AND SMOKE ALARM SYSTEM IN ACCORDANCE |
| | WITH THE REQUIREMENTS FOR AN R2 OCCUPANCY. FBC 907.2.9, |
| | 907.2.11 |
| | |
| | PROVIDE AN INDIVIDUAL BRANCH CIRCUIT PROTECTED BY A |
| | READILY ACCESSIBLE GFCI TO THE HYDRO MASSAGE TUB. NEC |
| | 680.71 |
| | |
| | PROVIDE AN ELECTRICAL BONDING PLAN FOR THE HYDRO |
| | MASSAGE TUB INSTALLATION. NEC 680.70.74 |
| | |
| | ALL RECEPTACLES LOCATED WITH SIX FEET OF THE HYDRO |
| | MASSAGE TUB SHALL BE PROTECTED BY A GFCI. NEC 680.71 |
| | |
| | PROVIDE A DETAIL ON THE PLAN WHICH SHOWS THE LOCATION |
| | AND CONSTRUCTION METHOD OF THE PROPOSED ACCESS PANEL |
| | FOR THE HYDRO MASSAGE TUBE ELECTRICAL PUMP AND GFCI |
| | RECEPTACLE. NEC 680.73 |
| | |