2017-06-06 14:54:47 
 17051281
 201 S. NARCISSUS AVE. #804
 INTERIOR REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 INDICATE THE SIZE, RATING, AND LOCATION OF THE EXISTING
 PANEL BOARD. VERIFY THE REQUIRED WORKING CLEARANCES ARE
 MAINTAINED AT THE ELECTRICAL PANEL. NEC 110.26
  
 VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC
 406.12
  
 VERIFY ALL NEW RECEPTACLE CIRCUITS ARE AFCI PROTECTED.
 NEC 210.12
  
 RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER
 REQUIRE GFCI PROTECTION. NEC 210.8
  
 VERIFY THE EXISTING AC UNITS HAVE THE REQUIRED
 DISCONNECTS. NEC 422.30
  
 VERIFY OR PROVIDE A 20 AMP LAUNDRY CIRCUIT WITH GFCI
 PROTECTION. NEC 210.11 (C) (2)
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON EACH
 BALCONY. NEC 210.8, 210.52(E)(3)
  
 PROVIDE A FIRE AND SMOKE ALARM SYSTEM IN ACCORDANCE
 WITH THE REQUIREMENTS FOR AN R2 OCCUPANCY. FBC 907.2.9,
 907.2.11
  
 PROVIDE AN INDIVIDUAL BRANCH CIRCUIT PROTECTED BY A
 READILY ACCESSIBLE GFCI TO THE HYDRO MASSAGE TUB. NEC
 680.71
  
 PROVIDE AN ELECTRICAL BONDING PLAN FOR THE HYDRO
 MASSAGE TUB INSTALLATION. NEC 680.70.74
  
 ALL RECEPTACLES LOCATED WITH SIX FEET OF THE HYDRO
 MASSAGE TUB SHALL BE PROTECTED BY A GFCI. NEC 680.71
  
 PROVIDE A DETAIL ON THE PLAN WHICH SHOWS THE LOCATION
 AND CONSTRUCTION METHOD OF THE PROPOSED ACCESS PANEL
 FOR THE HYDRO MASSAGE TUBE ELECTRICAL PUMP AND GFCI
 RECEPTACLE. NEC 680.73
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  