Plan Review Notes
Plan Review Notes For Permit 17051281
Permit Number 17051281
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-02 12:44:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A FAIR
 HOUSING.
  
 SEE FAIR HOUSING FAQ
 (HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML):
  
 8. DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF
 PROPERTIES?
 ALTERATIONS, REHABILITATION OR REPAIR OF COVERED
 MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S
 DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW
 CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY
 DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE
 LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT
 WITH THE LAW.
  
 2. ARCHITECT'S TITLE BLOCK LACKS INFORMATION REQUIRED
 BY FS481, FAC61G1-16.004, REVISE TO COMPLY.
  
 3. ID2.3 SHOWS WOOD FLOOR/CEILING JOISTS; ISN'T THIS A
 HIGH RISE NON COMBUSTIBLE BUILDING? FBC 107, FBC B 603.
  
 4. I WAS UNABLE TO FIND ANY INDICATION THAT THE
 FLOORING IS TO BE REPLACED. IF THAT IS THE CASE, REVISE
 PLAN TO NOTE THAT EXISTING FLOORING IS TO REMAIN. IF
 FLOORING IS PROPOSED, REVISE PLAN TO CLARIFY TYPE AND
 PROVIDE THE FOLLOWING TEST REPORTS FOR FLOORING
 UNDERLAYMENT:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  