| 2017-06-02 12:44:14 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A FAIR |
| | HOUSING. |
| | |
| | SEE FAIR HOUSING FAQ |
| | (HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML): |
| | |
| | 8. DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION |
| | REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF |
| | PROPERTIES? |
| | ALTERATIONS, REHABILITATION OR REPAIR OF COVERED |
| | MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S |
| | DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW |
| | CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY |
| | AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY |
| | DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE |
| | LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT |
| | WITH THE LAW. |
| | |
| | 2. ARCHITECT'S TITLE BLOCK LACKS INFORMATION REQUIRED |
| | BY FS481, FAC61G1-16.004, REVISE TO COMPLY. |
| | |
| | 3. ID2.3 SHOWS WOOD FLOOR/CEILING JOISTS; ISN'T THIS A |
| | HIGH RISE NON COMBUSTIBLE BUILDING? FBC 107, FBC B 603. |
| | |
| | 4. I WAS UNABLE TO FIND ANY INDICATION THAT THE |
| | FLOORING IS TO BE REPLACED. IF THAT IS THE CASE, REVISE |
| | PLAN TO NOTE THAT EXISTING FLOORING IS TO REMAIN. IF |
| | FLOORING IS PROPOSED, REVISE PLAN TO CLARIFY TYPE AND |
| | PROVIDE THE FOLLOWING TEST REPORTS FOR FLOORING |
| | UNDERLAYMENT: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |