| Plan Review Notes For Permit 17051249 |
| Permit Number |
17051249 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-31 07:51:38 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE DECK TYPE, THE SYSTEM NUMBER AND THE | | | MAXIMUM DESIGN PRESSURE OF THE ROOFING SYSTEM THAT WILL | | | BE INSTALLED FROM THE ONES LISTED IN THE PRODUCT | | | APPROVAL. FBC 107.2.1 | | | | | | 2) IF THIS IS A MECHANICALLY ATTACHED SYSTEM AND | | | ENHANCED FASTENING IS REQUIRED IN ORDER TO MEET THE | | | INCREASED UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3, THEN | | | SUBMIT TWO SETS OF SIGNED AND SEALED RAS117 | | | CALCULATIONS. FBC-R905.11.3 |
|