| Plan Review Notes For Permit 17051237 |
| Permit Number |
17051237 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-06 15:19:27 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIMPSON H7Z STRAPS THAT ARE SPECIFIED AS THE | | | ROOF TO WALL CONNECTORS ONLY PROVIDE RESISTANCE TO | | | LATERAL FORCES THAT ARE PARALLEL TO THE WALL. THEY DO | | | NOT RESIST LATERAL FORCES THAT ARE PERPENDICULAR TO THE | | | WALL. THESE CONNECTORS ARE ALSO REQUIRED TO BE STRAPPED | | | TO THE WALL STUDS. THE PLANS SPECIFY THE WALL STUDS TO | | | BE 16 INCHES ON CENTER AND THE ROOF TRUSSES ARE TO BE | | | 24 INCHES ON CENTER. THE H7Z STRAPS WON'T WORK BECAUSE | | | THE TRUSSES ARE NOT ALIGNED WITH THE WALL STUDS. | | | FBC-R802.1.7.5 | | | | | | 2) REVISED ENERGY FORMS SHOWING THE CHANGES WILL NEED | | | TO BE SUBMITTED AND REVIEWED. FBC ENERGY CONSERVATION | | | R103.2 |
|