Plan Review Notes
Plan Review Notes For Permit 17051237
Permit Number 17051237
Review Stop B
Sequence Number 2
Notes
Date Text
2017-07-06 15:19:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIMPSON H7Z STRAPS THAT ARE SPECIFIED AS THE
 ROOF TO WALL CONNECTORS ONLY PROVIDE RESISTANCE TO
 LATERAL FORCES THAT ARE PARALLEL TO THE WALL. THEY DO
 NOT RESIST LATERAL FORCES THAT ARE PERPENDICULAR TO THE
 WALL. THESE CONNECTORS ARE ALSO REQUIRED TO BE STRAPPED
 TO THE WALL STUDS. THE PLANS SPECIFY THE WALL STUDS TO
 BE 16 INCHES ON CENTER AND THE ROOF TRUSSES ARE TO BE
 24 INCHES ON CENTER. THE H7Z STRAPS WON'T WORK BECAUSE
 THE TRUSSES ARE NOT ALIGNED WITH THE WALL STUDS.
 FBC-R802.1.7.5
  
 2) REVISED ENERGY FORMS SHOWING THE CHANGES WILL NEED
 TO BE SUBMITTED AND REVIEWED. FBC ENERGY CONSERVATION
 R103.2